background image

Specifi cations

Model

PFG300

 series

Applicable SMC 
fl ow switch

Model

PFMC7501

PFMC7102

PFMC7202

Rated fl ow range

1

5 to 500 

l/

min

10 to 1000 

l/

min

20 to 2000 

l/

min

Flow

Set point 
range

Instantaneous fl ow

−25 to 525 

l/

min

−50 to 1050 

l/

min

−100 to 2100 

l/

min

Accumulated fl ow

0 to 999,999,999,990 L

Smallest settable 
increment

Instantaneous fl ow

l/

min

Accumulated fl ow

10 L

Accumulated volume per pulse 
(Pulse width = 50 ms)

1 L/pulse

10 L/pulse

Accumulated value hold function

3

Intervals of 2 or 5 minutes can be selected. The stored accumulated fl ow is held even when the power supply is OFF.

Electrical

Power supply voltage

12 to 24 VDC 

±

10 %

Current consumption

25 mA or less

Protection

Polarity protection

Accuracy

Display accuracy

±

0.5 % F.S. 

±

 Minimum display unit (Ambient temperature at 25

 

°C)

Analogue output accuracy

±

0.5 % F.S. (Ambient temperature at 25

 

°C)

Repeatability

±

0.1 % F.S. 

±

1 digit

Temperature characteristics

±

0.5 % F.S. (Ambient temperature: 0 to 50

 

°C, 25

 

°C standard)

Switch output

Output type

Select from NPN or PNP open collector output.

Output mode

Select from Hysteresis, Window comparator, Accumulated output, Accumulated pulse output, 

Error output, or Switch output OFF modes.

Switch operation

Select from Normal or Reversed output.

Max. load current

80 mA

Max. applied voltage (NPN only)

30 VDC

Internal voltage drop (Residual voltage)

NPN output: 1 V or less (at load current of 80 mA), PNP output: 1.5 V or less (at load current of 80 mA)

Response time

2

3 ms or less

Delay time

2

Select from 0.00, 0.05 to 0.1 s (increment of 0.01 s), 0.1 to 1.0 s (increment of 0.1 s), 1 to 10 s (increment of 1 s), 20 s, 30 s, 40 s, 50 s, or 60 s.

Hysteresis

4

Variable from 0

Protection

Short circuit protection

Analogue 
output

5

Output type

Voltage output: 1 to 5 V, 0 to 10 V (only when the power supply voltage is 24 VDC)

Current output: 4 to 20 mA

(0 

l/

min to maximum value of the rated fl ow)

Impedance

Voltage output

Output impedance: 1 k

Ω

Current output

Maximum load impedance: 300 

Ω

 (at power supply voltage of 12 V), 600 

Ω

 (at power supply voltage of 24 VDC)

Response time

2

50 ms or less

External input

6

External input

Input voltage: 0.4 V or less (Reed or Solid state) for 30 ms or longer

Input mode

Select from Accumulated value external reset or Peak/Bottom value reset.

Sensor input

Input type

Voltage input: 1 to 5 VDC (Input impedance: 1 M

Ω

), Current input: 4 to 20 mA DC (Input impedance: 51 

Ω

)

(0 

l/

min to maximum value of the rated fl ow)

Connection method

Connector (e-CON)

Protection

Over voltage protection (Up to 26.4 VDC)

Display

Display mode

Select from Instantaneous fl ow or Accumulated fl ow.

Unit

7

Instantaneous fl ow

l/

min, cfm (ft

3

/min)

Accumulated fl ow

L, ft

3

, L x 10

6

, ft

3

 x 10

6

Display
range

Instantaneous fl ow

−25 to 525 

l/

min

−50 to 1050 

l/

min

−100 to 2100 

l/

min

Accumulated fl ow

9

0 to 999,999,999,990 L

Minimum 
display unit

Instantaneous fl ow

l/

min

Accumulated fl ow

10 L

Display type

LCD

Number of displays

3-screen display (Main screen, Sub screen)

Display colour

1) Main screen: Red/Green, 2) Sub screen: Orange

Number of display digits

1) Main screen: 5 digits (7 segments), 2) Sub screen: 9 digits (7 segments)

Indicator LED

LED ON when switch output is ON. OUT1/2: Orange

Digital fi lter

8

Select from 0.00, 0.05 to 0.1 s (increment of 0.01 s), 0.1 to 1.0 s (increment of 0.1 s), 1 to 10 s (increment of 1 s), 20 s, or 30 s.

Environmental 
resistance

Enclosure

IP40

Withstand voltage

1000 VAC for 1 min between terminals and housing

Insulation resistance

50 M

Ω

 or more (500 VDC measured via megohmmeter) between terminals and housing

Operating temperature range

Operating: 0 to 50

 

°C, Stored: −10 to 60

 

°C (No condensation or freezing)

Operating humidity range

Operating/Stored: 35 to 85 % RH (No condensation or freezing)

Standards

CE marking (EMC directive/RoHS directive)

Weight

Body

25 g (Excluding the power supply/output connection lead wire)

Lead wire with connector

+39 g

1   Rated fl ow range of the applicable fl ow switch

2    Value without digital fi lter (at 0.00 s)

3   When using the accumulated value hold function, use the operating 

conditions to calculate the product life, and do not exceed it. The maximum 
access limit of the memory device is 1.5 million times. If the product is 
operated 24 hours per day, the product life will be as follows:

 5 min interval: life is calculated as 5 min x 1.5 million = 7.5 million min = 14.3 years

 2 min interval: life is calculated as 2 min x 1.5 million = 3 million min = 5.7 years

If the accumulated value external reset is repeatedly used, the product life 
will be shorter than the calculated life.

4    If the flow fluctuates around the set value, be sure to keep a sufficient 

margin. Otherwise, chattering will occur.

5    Setting is only possible for models with analogue output.

6    Setting is only possible for models with external input.

7    Setting is only possible for models with the units selection function.

8    The response time indicates when the set value is 90 % in relation to the step input.

9   The accumulated fl ow display is the upper 6-digit and lower 6-digit (total of 

12 digits) display. When the upper digits are displayed, x 10

6

 lights up.

    Products with tiny scratches, marks, or display colour or brightness variations  which 

do not affect the performance of the product are verifi ed as conforming products.

For fl ow switch precautions and specifi c product precautions, 
refer to the “Operation Manual” on the SMC website.

19

PFG300 

Series

Содержание PF2A Series

Страница 1: ...product Flow ratio 2 Smallest settable increment 10 1000 1000 L type 5 500 500 L type 5 l min for t PF2A serie l PFG300 Series RoHS min the for the existing es model l Digital Flow Monitor Allows for...

Страница 2: ...nding on application The accumulated indication shows the operating flow rate or residual amount of N2 etc in a gas cylinder Flow control of equipment main line and branch line Applications Remote con...

Страница 3: ...sub screen is set to mode display ModE LoC is displayed when the data storage lock is enabled Except for when the version does not match or when in SIO mode Display function Displays the output commun...

Страница 4: ...Visualization of settings Allows for the monitoring of remote lines Easy screen switching Simple 3 step setting Pressing the and buttons simultaneously for a minimum of 1 second will make the set valu...

Страница 5: ...e output free range function Error display function Copy function Selection of power saving mode Functions pp 26 to 28 Output operation Simple setting mode Display colour Delay time setting Digital fi...

Страница 6: ...flow type 1 l min PF2M7 L PFG300 PFG300 PF2A PF3A7 H L PFMB PFMC7 L 1 10 1 10 1000 1 20 2000 2 5 500 5 10 1000 1 20 2000 2 5 500 5 2 200 2 1 100 1 0 5 50 5 3 3 2 0 3 0 3 0 1 0 1 0 05 5 0 1 0 0 05 5 5...

Страница 7: ...Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Window comparator mode Variable Hysteresis mode Variable Win...

Страница 8: ...7...

Страница 9: ...L Series How to Order p 11 Specifications p 12 Flow Range p 13 Analogue Output p 13 Pressure Loss p 13 IN Side Straight Piping Length and Accuracy p 13 Internal Circuits and Wiring Examples p 14 Cons...

Страница 10: ...equired order with the part numbers listed below Part no Option Note ZS 40 A Lead wire with M8 connector Length 3 m ZS 42 A Bracket Mounting screw for PFMC7501 7102 M3 x 5 2 pcs ZS 42 B Bracket Mounti...

Страница 11: ...screen White Main screen 4 digits 7 segments Sub screen 6 digits 11 segments Indicator LED LED ON when switch output is ON OUT1 OUT2 Orange Environmental resistance Enclosure IP65 Withstand voltage 2...

Страница 12: ...erseas use only The SI unit type is provided for use in Japan in accordance with the New Measurement Act 7 Fixed units Instantaneous flow l min Accumulated flow L Calibration certificate None A 9 Yes...

Страница 13: ...2 The time from when the flow is changed by a step input when the flow rate changes from 0 to the maximum value of the rated flow range instantaneously until the analogue output reaches 90 of the rate...

Страница 14: ...A current flows it is possible that the accuracy is not satisfied below 0 5 V The minimum value of the rated flow range will change according to the setting of the zero cut function 0 l min A 2 B Volt...

Страница 15: ...Analogue 1 to 5 V output type PFMC7 C NPN 1 output Analogue 4 to 20 mA output type PFMC7 D Max applied voltage 28 V Max load current 80 mA Internal voltage drop 1 V or less C Analogue output 1 to 5 V...

Страница 16: ...1 5 V or less L3 Analogue output 1 to 5 V or 0 to 10 V Output impedance 1 k L4 Analogue output 4 to 20 mA Max load impedance 600 Min load impedance 50 Max applied voltage 30 V Max load current 80 mA I...

Страница 17: ...3 Flow rectifier Stainless steel 304 4 Sensor chip Silicon 5 Printed circuit board GE4F 6 Gasket HNBR 7 Body Aluminum alloy Anodized 8 Mesh Stainless steel 304 9 Spacer PPS 10 O ring HNBR 11 Holder St...

Страница 18: ...Material Heat and oil resistant PVC Finished outside diameter 4 Symbol Model Port size A B D E F H K L N PFMC7501 7102 L Rc1 2 NPT1 2 70 30 60 6 41 2 15 14 26 18 13 6 PFMC7202 L Rc3 4 NPT3 4 G3 4 90 3...

Страница 19: ...outputs NPN PNP switching type Analogue voltage output 1 2 SV 2 outputs NPN PNP switching type Analogue current output 2 XY 2 outputs NPN PNP switching type Copy function 1 Can switch between 1 to 5 V...

Страница 20: ...w Unit 7 Instantaneous flow l min cfm ft3 min Accumulated flow L ft3 L x 106 ft3 x 106 Display range Instantaneous flow 25 to 525 l min 50 to 1050 l min 100 to 2100 l min Accumulated flow 9 0 to 999 9...

Страница 21: ...Sensor Main circuit Main circuit Main circuit Load Load Load Load Load Load Load Load Load Load Load Load Load Load Max 28 V 80 mA Black OUT1 White OUT2 Blue DC Load Load Max 80 mA Brown DC Black OUT...

Страница 22: ...llows for mounting in four orientations Bracket configuration allows for mounting in four orientations 1 6 7 2 7 2 5 2 5 2 5 2 30 30 25 1 5 2 7 7 7 20 20 Sensor connector 4 x 2 6 Depth 7 or less Power...

Страница 23: ...Panel mount adapter Front protection cover Part no ZS 46 D Power supply output connection lead wire Part no ZS 46 5L Sensor connector Part no ZS 28 CA 4 1 1 to 5 V or 4 to 20 mA Pin no Terminal 1 DC...

Страница 24: ...s 24 or more 31 0 0 4 24 or more 31 x n pcs 3 5 x n pcs 1 4 x R 2 o r m o r e 31 0 0 4 Dimensions Multiple 2 pcs or more secure mounting Horizontal Panel mount example Horizontal Panel mount example...

Страница 25: ...external inputs and the accumulated value memorizing time interval should not exceed 1 million times Peak Bottom value reset Peak and bottom value are reset Forced output function The output is turned...

Страница 26: ...ing it on again OUT2 over current error A load current of 80 mA or more is applied to the switch output OUT2 Instantaneous flow error The flow has exceeded the upper limit of the flow display range De...

Страница 27: ...when OFF 1 V or 0 V when 0 to 10 V is selected or 4 mA Also an increase or decrease of the flow will not change the on off status of the output while the forced output function is activated Accumulat...

Страница 28: ...pply and then turning it on again Instantaneous flow error The flow rate exceeds the maximum value of the display range Decrease the flow rate Reverse flow error There is a reverse flow equivalent to...

Страница 29: ...o the slave monitors reducing setting labor and minimizing the risk of setting mistakes The set value can be copied to up to 10 flow monitors simultaneously Maximum transmission distance 4 m Selection...

Страница 30: ...of SMC products with production equipment for the manufacture of weapons of mass destruction WMD or any other weapon is strictly prohibited 2 The exports of SMC products or technology from one countr...

Страница 31: ...alia it Latvia 371 67817700 www smc lv info smc lv Lithuania 370 5 2308118 www smclt lt info smclt lt Netherlands 31 0 205318888 www smc nl info smc nl Norway 47 67129020 www smc norge no post smc nor...

Отзывы: