IN19856
- 20 -
Rev 2
Enter key and the ITV will automatically reboot. Note: Pressure or vacuum control will be
interrupted during the rebooting process. Other changes to network configuration may not be
stored at the same time as changing to or from compatibility mode.
15.
Setpoint and Feedback
Standard PLC Output Control Signal formatting (Setpoint)
INT 0
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Byte 0 - SINT
Byte 1 - SINT
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
LSb
Control Signal
MSb Ext
X
X
X
Note: “Ext” Used for extending the pressure range above 100% full scale
Standard PLC Input Control Signal formatting (Feedback)
INT 0
INT 1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Byte 0 - SINT
Byte 1 - SINT
Byte 2 - SINT
Byte 3 - SINT
0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7
L
Feedback
M E X X X
Diagnostics
Note: “E” Allows for to showing pressure greater than 100% full scale
16.
Byte Swap
Byte Swap
–
This is a legacy feature to match byte swap feature on the DUQ version of the ITV.
When box is checked, it will byte swap input and output into the ITV. Table below shows how this
works.
No Byte Swap - Little Endian
Byte Swapped - Big Endian
Output
Byte 0
1
Byte 1
0
Input
Byte 0
1
2
3
Byte 1
0
3
2