IN19856 

 

 - 15 - 

 

Rev 2 

9.1.

 

Dip Switches 

 

Dip switches set last octet of IP address - Default is 192.168.1.XXX 

 

Left most switch is 1 and the right most is 128 

 

The value of the dip switches is read at power up 

 

Numbers 1-254 are valid IP values 

 

Number 255 does nothing - Whatever value or mode the device is in it will stay that way on 

power up. 

 

Factory Default is 255 all switches on. 

 

Switch value zero will reset the IP address to it default value. - 192.168.1.20 

a. The subnet mask should also be set to default value - 255.255.0.0 

b. The Gateway should also be reset to default value - 0.0.0.0 

 

DHCP 

a. Dip switches must be in 255 for DHCP to work 

10.

 

Mounting and Plumbing 

 
For standard mounting, properly install pneumatic fittings in the threaded ports of the ITV base.  

For additional details see 

SMC Best Pneumatics

 version 5 (or later), volume 5, ITV Section Series 

ITV0000/1000/2000/3000.  For information about SMC fittings see 

http://www.smcusa.com/top-

navigation/cad-models.aspx/87051

.See Figure 4 - ITV20XX Drawing for the description of fitting 

ions.  Torque the fittings as indicated: 

 

Connection thread 

1/8 

1/4 

3/8 

1/2 

Torque (

N•m)

 

7 to 9 

12 to 14 

22 to 24 

28 to 30 

Figure 5 - Recommended proper connection torque: N•m

 

10.1.

 

Install pneumatic tubing

.   

When installing this tubing, be sure that the air pressure or vacuum source is 

LOCKED

 

OFF

 at the 

closest shutoff valve before the ITV.  There must be 

NO AIR PRESSURE OR VACUUM

 in the 

pneumatic line until all connections are complete. 

Caution

 

DO NOT

 enable air pressure or vacuum until 

ALL

 pneumatic lines in the circuit have 

been properly connected and the connections have been verified to be correct.  Failure 

to follow this requirement can result in injury or equipment damage.

 

Be 

SURE

 you understand the location and function of the ports 

BEFORE

 connecting the 

ITV to an air or vacuum line.  

VERIFY

 that these lines are properly connected 

BEFORE

 

enabling pneumatic pressure or vacuum and 

BEFORE

 powering the ITV.

 

 

 

 

Содержание ITV SEN DUX02357 Series

Страница 1: ...IN19856 1 Rev 2 PRODUCT NAME Ethernet ITV Ethernet IPTM MODEL Series Product Number ITVXXXX SEN XX DUX02357 XXXX...

Страница 2: ...______________ 16 13 Hold on Connection Loss ______________________________________________________________________ 19 14 Compatibility Mode ___________________________________________________________...

Страница 3: ...al rules relating to systems ISO 4413 Hydraulic fluid power General rules relating to systems IEC 60204 1 Safety of machinery Electrical equipment of machines Part 1 General requirements ISO 10218 199...

Страница 4: ...ed incorrectly The assembly operation and maintenance of machines or equipment including our products must be performed by an operator who is appropriately trained and experienced 3 Do not service or...

Страница 5: ...ified catalog for the products 1 Vacuum pads are excluded from this 1 year warranty A vacuum pad is a consumable part so it is warranted for a year after it is delivered Also even within the warranty...

Страница 6: ...le interlocking system for example a mechanical system Check the product regularly for proper operation Otherwise malfunction can result causing an accident The following instructions must be followed...

Страница 7: ...ghtening torque is exceeded the mounting screws may be broken IP65 protection cannot be guaranteed if the screws are not tightened to the specified torque Never mount a product in a location that will...

Страница 8: ...ctly use a fieldbus system with a built in surge absorbing element o Direct drive of a load generating surge voltage can damage the fieldbus system o The product is NOT immune to lightning strikes Tak...

Страница 9: ...ng the built in ITV web interface Examples for each of these conditions are documented in this manual This manual provides information for ITV setup and configuration examples of the web interface a L...

Страница 10: ...ue for each device to ensure proper operation of the network IPxy International Ingress Protection standard xy indicates the level of protection from external objects hands steel balls steel wire dust...

Страница 11: ...IN19856 11 Rev 2 5 How to Order Single ITV Options Assembled Manifold Mounted Options...

Страница 12: ...flying leads EX500 AP050 S 5m EX500 AP010 A 1m One end molded M12 right angle connector Other end flying leads EX500 AP050 A 5m Cable with Speedcon connector PCA 1401804 1 5 m One end molded M12 stra...

Страница 13: ...tion 2090 1 Exhaust Vacuum Port Exhaust Port X010 X030 X050 Vacuum Line Connection 2090 1 LED Display window Network and operating status LEDs 2 Fieldbus interface connector Bus In Ethernet connection...

Страница 14: ...ing that IP address into the address bar of a computer that is connected to the same network and on the same subnet 4 Login as user password user then select network tab to change the IP address 5 The...

Страница 15: ...0 For information about SMC fittings see http www smcusa com top navigation cad models aspx 87051 See Figure 4 ITV20XX Drawing for the description of fitting ions Torque the fittings as indicated Conn...

Страница 16: ...n 1 TD Transmit Data 2 RD Receive Data 3 TD Transmit Data 4 RD Receive Data Figure 7 ITV Ethernet Cable Pin Signals Use a standard industrial Ethernet cable For cable selection see Accessories Connect...

Страница 17: ...standard and therefore is not compatible with these devices The ITV Power Over Ethernet POE implementation is unique to the SMC ITV Do NOT operate other devices using the ITV POE Do NOT use POE from...

Страница 18: ...indicated by the Enable POE checkbox enabled 24 VDC on checked or disabled 24 VDC off unchecked 12 3 Connecting ITVs for a POE Group The cable connections are critical for proper operation of POE The...

Страница 19: ...the group EXCEPT THE FINAL ITV MUST have POE ENABLED The FINAL ITV MUST have POE DISABLED Caution POE for the FINAL ITV in a ITV POE group must be disabled for proper operation 7 A power supply connec...

Страница 20: ...e pressure range above 100 full scale Standard PLC Input Control Signal formatting Feedback INT 0 INT 1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Byte 0 SINT Byte 1 S...

Страница 21: ...etween the User Sensitivity values of 0 to 7 18 Setpoint and Feedback Setpoint is the requested value for the ITV s regulated pressure or vacuum output An external master typically a PLC sends the set...

Страница 22: ...ed by using the Scale Factor Formula The following table shows some precalculated the scale factors for the ITV body types and pressure units Pressure Body Type MPa kg cm2 Bar PSI KPa X010 40950 0 401...

Страница 23: ...ng Below is how to set the ITV to engineering unit mode using the webpage Refer to Explicit Messaging to config from the PLC Note Changing to and from engineering mode should be done without a setpoin...

Страница 24: ...es below for a full description with an example following ITV Unit Type 0 1 MPa Engineering Units MPa Kg cm 2 BAR PSI kPa Counts Multiplier 100000 10000 10000 1000 100 See Section 18 1 ITV Unit Type 0...

Страница 25: ...ermined by what ITV unit type you re using and what engineering units you wish to send 18 5 Engineering Units as Feedback When an engineering unit is selected as outlined above the unit type that was...

Страница 26: ...all values between 100 to 120 are linear Note 120 of the vacuum regulator is an impossibility as there is not enough difference in the vacuum pressure for the ITV to function correctly ITV Unit Type...

Страница 27: ...imes lowering the sensitivity number too much can cause the ITV to hunt and be less precise The larger the sensitivity number the less likely hunting will occur but the precision will be reduced 19 2...

Страница 28: ...he ITV operating voltage is not supplied or the ITV is in DHCP mode with NO valid IP address set Green ON Communication established Green flashing Idle link Red flashing Communication time out Red ON...

Страница 29: ...age not supplied terminal is not connected to another operating device or terminal failed Bus In Bus Out Green ON Terminal is connected to another operating device Bus In Bus Out Yellow Flashing Inter...

Страница 30: ...Enter the IP address of the ITV into your internet browser as shown below Default address is 192 168 1 20 The System Information page will open Select and press Login button at the upper right corner...

Страница 31: ...the Network page will be displayed to show the communication and connection status of the ITV On this page login network configuration and operating parameters can be changed Figure 17 ITV Network web...

Страница 32: ...f POE may result in undesired performance abnormal equipment operation or product damage Hold on Connection Loss checkbox is used to control ITV behavior in the event Ethernet communication is lost to...

Страница 33: ...rrent feedback pressure from the ITV in the unit type selected above Pressure Setpoint Shows the current setpoint set via the PLC unless the Override PLC Control is enabled If the pressure setpoint va...

Страница 34: ...ged press submit button for the change to take effect If the user gain value entered is legitimate the user gain will be submitted to the ITV for pressure or vacuum regulation If the user gain value i...

Страница 35: ...IN19856 35 Rev 2 Figure 29 ITV Login Management web page...

Страница 36: ...using RSLogix 5000 or Logix DesignerTM software by Rockwell Automation refer to Rockwell Automation manuals for detailed operation 1 Example of configuring with EDS file Select EDS Hardware Installat...

Страница 37: ...2 Select the EDS file to be installed and select Next Figure 21 Select EDS File to Install Right click on the selection Ethernet in the I O Configuration folder and select New Module Figure 22 New Mo...

Страница 38: ...XXX SEN XX DUX02357 and select Create Figure 23 Select Module Type Screen When the New Module screen is displayed input the information below 1 Name Enter the required unit name 2 IP Address The IP ad...

Страница 39: ...le Definition Screen 2 Example of setting using the Generic Ethernet Module Right click on the selection Ethernet in the I O Configuration folder and select New Module The Select Module Type screen is...

Страница 40: ...ta format of Comm Connection Parameters 3 IP Address Enter the IP address setting for the SI unit 4 Assembly Instance Perform setting as shown below Description Decimal Input 150 Output 100 Configurat...

Страница 41: ...2v equal 242 Figure 28 Available Explicit Messages 23 1 Diagnostics Bit Description Extended Description Persistent 0 Setpoint signal error Setpoint Values out of range If Setpoint greater than 120 f...

Страница 42: ...Pressure Unit Counts Engineering Unit Counts User Gain 8 User Sensitivity 2 Webpage ID user Webpage Password user Figure 32 ITV Initial Configuration Appendix 24 Explicit Message Example using LabVIE...

Страница 43: ...ware Industrial Communications library is used to set and get explicit messages to and from the ITV 25 Scaling Here are some example graphs to help with understanding how to scale the input and output...

Страница 44: ...ssure MPa ITV 010 COUNT SCALING 0 819 1638 2457 3276 4095 4914 0 1000 2000 3000 4000 5000 6000 0 00 0 10 0 20 0 30 0 40 0 50 0 60 Counts 16 bit Number Pressure MPa ITV 030 COUNT SCALING 0 819 1638 245...

Страница 45: ...sure there are no breaks or cuts in the power cable 3 If the ITV is being powered using POE be sure that the requirements of POE are met In particular ensure that the upstream ITV has POE enabled and...

Страница 46: ...may not be high enough for the ITV to operate properly Verify the ITV power is within specification 26 5 Problem Unable to Communicate with ITV Symptom LEDs are Green ITV does not respond to commands...

Страница 47: ...1 Verify the correct formula for calculating pressure is used for determining pressure value See the conversions in Basic PLC Configuration Possible Cause Pressure Change in Progress 1 If the master r...

Страница 48: ...exhausted from the ITV exhaust port 5 If the problem persists contact SMC Technical Support for assistance This is not an exhaustive troubleshooting guide SMC Technical Support may request that you c...

Страница 49: ...e ITV Set all the dip switches down or off or 0 Power on the ITV Wait for the MS LED to start to flash green Power off the ITV Set the dip switches to all up or On or 1 ITV should now be back to defau...

Страница 50: ...onnector 2 One 1 Ethernet cable with a 4 pin male M12 D Coded connector on one end and a standard LAN Ethernet cable plugin connector RJ45 on the other end 3 A PC with a LAN port The PC is either dire...

Страница 51: ...ws may differ describe how to set the PC to subnet 1 Note If the PC is already configured to use subnet 1 you may skip this section This procedure assumes that you have appropriate access privileges o...

Страница 52: ...a result your view may be somewhat different from the following window If you have questions please review the documentation for your PC If you have additional questions please consult your PC or Net...

Страница 53: ...e Local Area Connection Properties window will appear Figure 35 Windows Local Area Connection and Local Area Connection Properties Next select Internet Protocol Version 4 TCP IPv4 and press the Proper...

Страница 54: ...otocol IPv4 Properties and type the new value Do NOT hit the keyboard Enter key That has the effect of pressing the OK button but does not give you the opportunity to review your Subnet change to ensu...

Страница 55: ...ch your preferred browser The following examples use Google Chrome Firefox and IE are similar Figure 37 Chrome Browser Homepage In order to bring up the ITV web page type the ITV IP address on the bro...

Страница 56: ...ormation page does NOT appear please see the following subsections ITV Does Not Power Up One LED is Red If necessary contact SMC Technical Support for assistance Note To change the ITV IP address foll...

Страница 57: ...ion Date 2 Added How to order for IITV 09 02 2020 1 Updates for DUX 08 01 2020 0 Initial release for EthernetIPTM ITV 10 30 2019 SMC Corporation of America 10100 SMC Boulevard Noblesville IN 46060 Pho...

Страница 58: ...IN19856 58 Rev 2...

Отзывы: