HRX-OM-Q033
Chapter 2 Contact input/output communication
2.6
Contact output signal
HRSH Series
2-20
Table 2.6-2
Operation of contact output signal
Class of signal
Operation of contact output signal
Display
Function
Oper
ation
OFF
Without
signal
output
N.O
type
Normally, output signal is OFF (open)
N.C
type
Normally, output signal is ON (close)
RUN
Operation
status
signal output
N.O
type
When the product operates, signal turns ON.
N.C
type
When the product operates, signal turns OFF.
RMT
Remote
status
signal output
N.O
type
When the product becomes DIO REMOTE, signal turns ON.
N.C
type
When the product becomes DIO REMOTE, signal turns OFF.
RDY
Ready completion
(TEMP
READY)
signal output
N.O
type
When the product becomes the status of ready completion
(TEMP READY), signal turns ON.
N.C
type
When the product becomes the status of ready completion
(TEMP READY), signal turns OFF.
A.STP
Operation
stop
alarm signal output
N.O
type
When operation stop alarm occurs, signal turns ON.
N.C
type
When operation stop alarm occurs, signal turns OFF.
A.RUN
Operation
continuation alarm
signal output
N.O
type
When operation continuation alarm occurs, signal turns ON.
N.C
type
When operation continuation alarm occurs, signal turns OFF.
ALM
Alarm status signal
output
N.O
type
When alarm occurs, signal turns ON.
N.C
type
When alarm occurs, signal turns OFF.
A.SEL
Selected
alarm
status signal output
N.O
type
When selected alarm occurs, signal turns ON.
N.C
type
When selected alarm occurs, signal urns ON.
ON.TM
Operation
start
timer setting status
signal output
N.O
type
When run timer is set, signal turns ON.
N.C
type
When run timer is set, signal turns OFF.
OF.TM
Operation
stop
timer setting status
signal output
N.O
type
When stop timer is set, signal turns ON.
N.C
type
When stop timer is set, signal turns OFF.
P.RST
Recovery
from
power
failure
setting status signal
output
N.O
type
When recovery from power failure is set, signal turns ON.
N.C
type
When recovery from power failure is set, signal turns OFF.
F.P.
Anti-freezing setting
status signal output
N.O
type
When anti-freezing function is set, signal turns ON.
N.C
type
When anti-freezing function is set, signal turns OFF.
INP1.
1
Contact input signal
1
pass
through
signal output
N.O
type
Outputs the same signal as input one to the contact input
signal 1. Input signal is ON
Output signal is ON
N.C
type
Outputs the opposite signal of input one to the contact input
signal 1.
Input signal is OFF
Output signal is ON
INP2
1
Contact input signal
2
pass
through
signal output
N.O
type
Outputs the same signal as input one to the contact input
signal 2. Input signal is ON
Output signal is ON
N.C
type
Outputs the opposite signal of input one to the contact input
signal 2.
Input signal is OFF
Output signal is ON
WARM
Warming up
function setting
status output
N.O
type
When warming up function is set, signal turns ON.
N.C
type
When warming up function is set, signal turns OFF.
SNOW
2
Anti-snow coverage
function
setting
status output
N.O
type
When anti-snow coverage function is set, signal turns ON.
N.C
type
When anti-snow coverage function is set, signal turns OFF.
1: The signal can not output normally when selected momentary.
2: Anti-snow coverage function cannot be set on the products of the cooling method
‘-W’.