HRX-OM-Q033
Chapter 2 Contact input/output communication
HRSH Series
2.4
Setting and checking
2-7
Contact input signal 1 delay timer of reading
Setting
and checking
7.
Press the [SEL] key once.
The set screen of the contact input signal 1 delay timer of reading is displayed on the digital
display.
8.
Select contact input signal 1 d
elay timer of reading from the table below with [▲] key or [▼]
key, and con
firm by pressing “SEL”.
Table 2.4-5
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input signal 1 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 1 delay timer of
reading.
Set range is 0 to 300 sec.
Contact input signal 1 OFF detection timer
Setting and checking
9.
Press the [SEL] key once.
The set screen of the contact input signal 1 OFF detection timer is displayed on the digital
display.
10.
Select contact input signal 1 OFF d
etection timer from the table below with [▲] key or [▼]
key, and confirm by pressing “SEL”.
Table 2.4-6
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting and checking are not available unless
contact input signal 1 is external switch signal
input (N.O. type or N.C. type).
to
Setting of contact input signal 1 OFF
detection timer
Set range is 0 to 10sec.
PV
SV
PV
SV