SMC Networks HECR Series Скачать руководство пользователя страница 6

5

1. How much is the temperature in degrees centigrade for the circulating fluid?

Thermo-con/

Series 

HEC

For details, refer to 

the WEB catalog or the Best Pneumatics No. 7. 

±

0.018°F 

to

 0.054°F

(

±

0.01°C to 0.03°C)

Circulating fluids that can be used in the Thermo-con: Water, Ethylene glycol 20%
When using fluorinated fluids, select the water-cooled Thermo-con HEC series.

2. What kind of the circulating fluids will be used?

Allows a safety factor of 2 0 % over the capacity that is actually required, taking into account the changes in the operating 
conditions. If a larger capacity than this Thermo-con is necessary, select the Peltier-type Thermo-con HEC series (refer to 
the following.) or the refrigerated Thermo-chiller HRS/HRZ series.

3. How much cooling capacity required?

Guide to Model Selection

Cooling capacity =  Considering a safety factor of 20%, 

400 W x 1.2 =  480 W

Series 

HECR

Model Selection

Air-cooled

Water-cooled

Example 1 When the heat generation amount in the user’s equipment is known.

Heat generation amount: 400 W

Temperature range which can be set with the Thermo-con: 50 to 140°F (10 to 60°C)
If a lower temperature (down to –4 °F [–20°C]) or higher temperature (up to 194°F [90°C]) than this range is necessary, select the 
Thermo-chiller HRZ series.

• Cooling capacity: 

140 

W

 to 1200 

W

• Temperature stability: 

High-precision temperature control type for semiconductor 
manufacturing equipment, medical equipment, etc.

Содержание HECR Series

Страница 1: ...18to 0 054 F 0 01 to 0 03 C Temperature stability 50 to 140 F 10 to 60 C Set temperature range 200 w Cooling capacity 440 w 100 V input 4 6 A Power consumption Energy saving Good space utilization Hei...

Страница 2: ...uid volume can be checked q Turn the power ON w Press the SEL key and adjust the temperature setting with the keys e Press the RET key to complete Canpreciselycontrolthetemperatureofaheatsourceorproce...

Страница 3: ...poses a Peltier device thermo module between the heat exchangers for the circulating fluid and facility water and controls the DC power supply to achieve the target outlet temperature of circulating f...

Страница 4: ...aling Electronic microscope Ultra sonic wave inspection machine Cooling of laser irradiated part Temperature control of X ray tube and X ray light sensing part Cooling of laser irradiated part Cooling...

Страница 5: ...pacity Page 8 Heating Capacity Page 8 Pump Capacity Thermo con Outlet Page 8 Dimensions Page 9 Operation Display Panel Page 10 Alarm Page 10 Maintenance Page 10 Options With Feet and No Rack Mounting...

Страница 6: ...ssary select the Peltier type Thermo con HEC series refer to the following or the refrigerated Thermo chiller HRS HRZ series 3 How much cooling capacity required Guide to Model Selection Cooling capac...

Страница 7: ...x 103 x 4 2 x 103 60 x 1000 167 W 200 W Cooling capacity Considering a safety factor of 20 167 W x 1 2 Water Density 1 x 103 kg m3 Specific heat C 4 2 x 103 J kg K Cooled substance total volume V Cool...

Страница 8: ...ty Note 2 0 018 to 0 054 0 01 to 0 03 C Pump capacity Refer to the performance charts Page 8 Tank capacity Approx 0 34 gal 1 3 L Port size Rc1 4 Wetted parts material Stainless steel EPDM Ceramics PPE...

Страница 9: ...300 200 100 0 0 Circulating fluid Water Ambient temperature 59 F 15 C Ambient temperature 95 F 35 F Heating capacity W 1000 900 800 700 600 500 400 300 200 100 0 0 Circulating fluid Ethylene glycol 2...

Страница 10: ...ng removing the product to from the rack Circulating fluid inlet Circulating fluid drain port Rc1 4 Circulating fluid outlet Rc1 4 Dimensions HECR002 A5 1 Power supply connector IEC60320 C14 or equiva...

Страница 11: ...disconnected or short circuited ERR18 External temp sensor disconnection alarm Continue The external temperature sensor has been disconnected or short circuited Only detected when in learning control...

Страница 12: ...kets and handles on the front side are removed as they are not necessary when the product is not mounted in a rack This option has rubber feet for installing the product on the floor E F F HECR002 A5...

Страница 13: ...e connector on the Thermo con side in position For single phase 200 VAC type Also applicable for the 100 VAC type but the connector for the user s equipment needs to be prepared by the user Part no Ap...

Страница 14: ...he product weight is held with the bottom surface of the product Use the handles on the front side of the product when installing removing the product to from the rack 1 The inlet for radiation air mu...

Страница 15: ...tank is made of resin PE Therefore the tank may be crushed if the pressure is negative Special attention must be paid if the flow rate of the circulating fluid is high To avoid getting negative press...

Страница 16: ...on or equipment in contact with food and beverages emergency stop circuits clutch and brake circuits in press applications safety equipment or other applications unsuitable for the standard specificat...

Отзывы: