Specific Product Precautions 1

Be sure to read this before handling. Refer to the back cover for Safety Instructions. For Temperature Control Equipment 
Precautions, refer to “Handling Precautions for SMC Products” and the Operation Manual on SMC website, 
http://www.smcworld.com

Transportation/Movement/Installation

Caution

Radiation Air

Caution

Circulating Fluid

Caution

System Design

Warning

Handling

Warning

Operating Environment/Storage Environment

Warning

1. This catalog shows the specifications of the 

Thermo-con.

1. Check the detailed specifications in the separate “Product 

Specifications”, and evaluate the compatibility of the Thermo-con 
with user’s system.

2. Although the protection circuit as a single unit is installed, the user is 

requested to carry out the safety design for the whole system.

1. Thoroughly read the Operation Manual. 

Read the Operation Manual completely before operation, and keep 
this manual available whenever necessary.

2. If the set temperature is repeatedly changed by 50°F 

(10°C) or more, the Thermo-con may fail in short 
periods of time.

1. Keep within the specified ambient temperature and 

humidity range.

Also, if the set temperature is too low, condensation may form on 
the inside of the Thermo-con or the surface of piping even within the 
specified ambient temperature range. Dew condensation can cause 
failure, and so must be avoided by considering operating conditions.

2. The Thermo-con is not designed for clean room 

usage.

The pump and fan generate dust.

3. Low molecular siloxane can damage the contact of 

the relay.

Use the Thermo-con in a place free from low molecular siloxane.

1. Avoid strong vibration and/or impact.

The product is precision equipment. Do not apply vibration or impact 
during transportation.

2. Caution when moving a heavy object.

This product is heavy. Use adequate caution to avoid injury when 
picking up and setting down the product, and dropping accidents 
should be avoided.

3. Installation

When installing the product into a rack, it should be designed that 
the product weight is held with the bottom surface of the product. 
Use the handles on the front side of the product when 
installing/removing the product to/from the rack.

1. The inlet for radiation air must not be exposed to 

particles and dust as far as possible.

2. Do not let the inlet and outlet for radiation air get 

closed.

3. If more than one Thermo-con is used, consider their 

arrangement so that the downstream sides of the 
Thermo-cons suck radiation air from the upstream 
sides.

Otherwise, the performance at the downstream sides may 
deteriorate. Also, the set temperature may not be achieved 
depending on the value of the set temperature and the load. In such 
a case, take countermeasures such as changing the direction of the 
Thermo-cons to prevent the deterioration of performance.

4. Filters are not built-in. Mount them as necessary.
5. Flow rate of the heat dissipation air is approximately 2 

m

3

/min. The heat generation is approximately 600 W at 

maximum.

1. Use a fluid that is listed in the specifications.
2. Deionized water (with an electrical conductivity of 

approximately 1 µS/cm) can be used, but may lose its 
electrical conductivity.

Also, if a facility supplying deionized water is used, the Thermo-con 
may be damaged by static electricity.

3. If deionized water is used, bacteria and algae may 

grow in a short period.

If the Thermo-con is operated with bacteria and algae, its cooling 
capacity or the capacity of the pump may deteriorate.
Exchange all deionized water regularly depending on the conditions 
(once a month as a guide).

4. If using a fluid other than those listed in the 

specifications, please contact SMC beforehand.

5. The maximum operating pressure of circulating fluid 

circuit is 15 psi (0.1 MPa).

If this pressure is exceeded, leakage from the tank in the 
Thermo-con can result.

6. Select a pipe with a length and diameter which allow a 

flow rate of 0.13 gal/min (0.5 L/min) or more for the 
circulating fluid.

If the flow rate is less than 0.13 gal/mon (0.5 L/min), the Thermo-con 
cannot provide precise control, but also can fail because of the 
repeated cooling and heating operation.

7. A magnet driven pump is used as a circulating pump.

A fluid which contains metal powders such as iron powder cannot be 
used.

13

Содержание HECR Series

Страница 1: ...18to 0 054 F 0 01 to 0 03 C Temperature stability 50 to 140 F 10 to 60 C Set temperature range 200 w Cooling capacity 440 w 100 V input 4 6 A Power consumption Energy saving Good space utilization Hei...

Страница 2: ...uid volume can be checked q Turn the power ON w Press the SEL key and adjust the temperature setting with the keys e Press the RET key to complete Canpreciselycontrolthetemperatureofaheatsourceorproce...

Страница 3: ...poses a Peltier device thermo module between the heat exchangers for the circulating fluid and facility water and controls the DC power supply to achieve the target outlet temperature of circulating f...

Страница 4: ...aling Electronic microscope Ultra sonic wave inspection machine Cooling of laser irradiated part Temperature control of X ray tube and X ray light sensing part Cooling of laser irradiated part Cooling...

Страница 5: ...pacity Page 8 Heating Capacity Page 8 Pump Capacity Thermo con Outlet Page 8 Dimensions Page 9 Operation Display Panel Page 10 Alarm Page 10 Maintenance Page 10 Options With Feet and No Rack Mounting...

Страница 6: ...ssary select the Peltier type Thermo con HEC series refer to the following or the refrigerated Thermo chiller HRS HRZ series 3 How much cooling capacity required Guide to Model Selection Cooling capac...

Страница 7: ...x 103 x 4 2 x 103 60 x 1000 167 W 200 W Cooling capacity Considering a safety factor of 20 167 W x 1 2 Water Density 1 x 103 kg m3 Specific heat C 4 2 x 103 J kg K Cooled substance total volume V Cool...

Страница 8: ...ty Note 2 0 018 to 0 054 0 01 to 0 03 C Pump capacity Refer to the performance charts Page 8 Tank capacity Approx 0 34 gal 1 3 L Port size Rc1 4 Wetted parts material Stainless steel EPDM Ceramics PPE...

Страница 9: ...300 200 100 0 0 Circulating fluid Water Ambient temperature 59 F 15 C Ambient temperature 95 F 35 F Heating capacity W 1000 900 800 700 600 500 400 300 200 100 0 0 Circulating fluid Ethylene glycol 2...

Страница 10: ...ng removing the product to from the rack Circulating fluid inlet Circulating fluid drain port Rc1 4 Circulating fluid outlet Rc1 4 Dimensions HECR002 A5 1 Power supply connector IEC60320 C14 or equiva...

Страница 11: ...disconnected or short circuited ERR18 External temp sensor disconnection alarm Continue The external temperature sensor has been disconnected or short circuited Only detected when in learning control...

Страница 12: ...kets and handles on the front side are removed as they are not necessary when the product is not mounted in a rack This option has rubber feet for installing the product on the floor E F F HECR002 A5...

Страница 13: ...e connector on the Thermo con side in position For single phase 200 VAC type Also applicable for the 100 VAC type but the connector for the user s equipment needs to be prepared by the user Part no Ap...

Страница 14: ...he product weight is held with the bottom surface of the product Use the handles on the front side of the product when installing removing the product to from the rack 1 The inlet for radiation air mu...

Страница 15: ...tank is made of resin PE Therefore the tank may be crushed if the pressure is negative Special attention must be paid if the flow rate of the circulating fluid is high To avoid getting negative press...

Страница 16: ...on or equipment in contact with food and beverages emergency stop circuits clutch and brake circuits in press applications safety equipment or other applications unsuitable for the standard specificat...

Отзывы: