QuickServer Start-Up Guide
Page 11 of 34
4.4 Power Up the Device
Check power requirements in the table below:
Power Requirement for External Gateway
Current Draw Type
QuickServer Family
12VDC
24V DC/AC
FS-QS-2X10-XXXX (Typical)
250mA
125mA
NOTE:
These values are ‘nominal’ and a safety margin should be added to the power supply of
the host system. A safety margin of 25% is recommended.
Figure 6: Required Current Draw for the Gateway
Apply power to the QuickServer as shown below in
Figure 7
.
Ensure that the power supply used
complies with the specifications provided in
Appendix C.5
.
•
The gateway accepts 12-24VDC or 24VAC on pins 4 and 5.
•
Frame GND should be connected.
Power to
Gateway
Gateway
Pin #
Pin
Assignment
Power In (+)
Pin 4
V +
Power In (-)
Pin 5
V -
Frame Ground
Pin 6
FRAME GND
Figure 7: Power Connections