•EX600-DX E /EX600-DX F  

 

Display

 

Content

 

 

ST LED is OFF

 

The power supply for control and input is OFF.

 

 

Green LED is ON

 

The product is operating normally.

 

 

Red LED is ON

 

The power supply of input device has a short circuit. 
(Each of input 0 to 15)

 

 

Red LED is flashing

 

The input device ON/OFF count has exceeded the set value. 
(Each of input 0 to 15)

 

 

“0 to 15” LEDs are OFF

 

The input device is OFF. 
(Each LED display number corresponds to input 0 to 15.) 

 

“0 to 15” green LEDs are ON

 

The input device is ON. 
(Each LED display number corresponds to input 0 to 15.)

 

: Refer to troubleshooting (SI unit Operation Manual of protocol used) for the further details of countermeasures.

 

Содержание EX600-DM Series

Страница 1: ...No EX OMN0036 Fieldbus system Digital unit PRODUCT NAME EX600 DX EX600 DY EX600 DM MODEL Series...

Страница 2: ...Wiring 20 LED Display 25 Specification 28 Specifications 28 Dimensions 31 Digital output unit Model Indication and How to Order 34 Names and Functions of Product 34 Mounting and Installation 36 Wirin...

Страница 3: ...2 No EX OMN0036 Common items Maintenance 57 Troubleshooting 58 Parameter Setting 58 I O Map 58 Diagnostic 58 Accessories 58 Precautions before mounting 59...

Страница 4: ...continuously review all specifications of the product referring to its latest catalog information with a view to giving due consideration to any possibility of equipment failure when configuring the e...

Страница 5: ...rts Please consult your nearest sales branch 2 For any failure or damage reported within the warranty period which is clearly our responsibility a replacement product or necessary parts will be provid...

Страница 6: ...e product outside of the specifications Do not use for flammable or harmful fluids Fire malfunction or damage to the product can result Verify the specifications before use Do not operate in an atmosp...

Страница 7: ...instructions on design and selection installation wiring environment adjustment operation maintenance etc described below must also be followed Product specifications The direct current power supply...

Страница 8: ...proper insulation of wiring Poor insulation interference from another circuit poor insulation between terminals etc can lead to excess voltage or current being applied to the product causing damage T...

Страница 9: ...es by using a sharp pointed screwdriver etc When setting the switch do not touch other unrelated parts This can cause parts damage or malfunction due to a short circuit Perform settings suitable for t...

Страница 10: ...th switch output capability PNP and NPN types are available Digital output unit For connecting output device such as solenoid valves lamps buzzers etc PNP and NPN types are available Digital I O unit...

Страница 11: ...unit to the end plate The Digital unit Analog unit can be connected in any order Tighten the bracket of the joint using tightening torque 1 5 to 1 6 Nm 2 Add more units Up to 10 units including the S...

Страница 12: ...C2000 3 places VQC4000 4 places SY 2 places 5 Connect the SI unit and the valve manifold Insert the valve plate to the valve plate set groove on the side of SI unit Then tighten it with the valve plat...

Страница 13: ...reinforcing brace EX600 ZMB1 before mounting using 2 M4x5 screws Tightening torque 0 7 to 0 8 Nm Intermediate reinforcing brace EX600 ZMB1 2 Fix and tighten the end plates at one end of the unit M4 T...

Страница 14: ...late bracket EX600 ZMA2 to the end plate at the opposite end to the valves using 2 M4x14 screws Tightening torque 0 7 to 0 8 Nm 3 Hook the DIN rail mounting groove to the DIN rail 4 Press the manifold...

Страница 15: ...turned 180 degrees 1 2 turn wiring is completed Confirm that the connection is not loose If turned too far it will become hard to remove the connector 1 2 3 D sub socket connection method is explained...

Страница 16: ...15 No EX OMN0036 Spring type terminal connection method is explained below...

Страница 17: ...each unit Mount the marker EX600 ZT1 into the marker groove as required Precautions for handling To open the clamp use a flat blade screwdriver of blade width 2 5 mm and thickness of 0 4 mm or less A...

Страница 18: ...nector 3 pin 8 inputs Yes D 8xM12 connector 5 pin 16 inputs No E D sub connector 25 pin 16 inputs No F Spring type terminals 32 pin 16 inputs No An M12 connector 4 pin can also be connected Names and...

Страница 19: ...t for joining to adjacent units 5 Unit connector Plug Transmits signals and power supplies to adjacent units EX600 DX D No Description Function 1 Status display LED Displays the status of the unit 2 C...

Страница 20: ...C 5 Joint bracket Bracket for joining to adjacent units 6 Unit connector Plug Transmits signals and power supplies to adjacent units EX600 DX F No Description Function 1 Status display LED Displays th...

Страница 21: ...Pin number Signal name 1 24 V Control and input 2 Input 2 3 0 V Control and input 4 Input 1 5 FE An M12 connector 4 pin can also be connected Circuit diagram EX600 DXPB EX600 DXPD EX600 DXNB EX600 DX...

Страница 22: ...ecification Note the following points when using the open circuit detection The 2 wire type input device cannot be correctly detected if its leakage current is 0 5 mA or less while the equipment is in...

Страница 23: ...put 8 6 Input 10 7 Input 12 8 Input 14 9 NC 10 24 V Control and input 11 0 V Control and input 12 0 V Control and input 13 FE 14 Input 1 15 Input 3 16 Input 5 17 Input 7 18 Input 9 19 Input 11 20 Inpu...

Страница 24: ...Control and input X2 2 Input 4 3 Input 5 2 4 0 V Control and input X2 1 24 V Control and input X3 2 Input 6 3 Input 7 3 4 0 V Control and input X3 1 24 V Control and input X4 2 Input 8 3 Input 9 4 4 0...

Страница 25: ...24 No EX OMN0036 Circuit diagram EX600 DXPF EX600 DXNF...

Страница 26: ...ce is ON Red LEDs are ON EX600 DX C1 The power supply of input device has a short circuit Models other than EX600 DX C1 The power supply of either input device of adjoined LED has a short circuit Red...

Страница 27: ...ED is ON The input device is ON Red LEDs are ON The power supply of either input device of adjoined up and down LED has a short circuit Red LED is flashing The input device ON OFF count has exceeded t...

Страница 28: ...Each of input 0 to 15 Red LED is flashing The input device ON OFF count has exceeded the set value Each of input 0 to 15 0 to 15 LEDs are OFF The input device is OFF Each LED display number correspon...

Страница 29: ...V 2 wire 0 5 mA input 2 Input specifications Open circuit detection current 3 wire 0 5 mA Connector 2 Current consumption 50 mA or less 55 mA or less 70 mA or less Enclosure IP67 With manifold assembl...

Страница 30: ...Applicable wire 0 08 to 1 5 mm 2 AWG 16 to 28 Current consumption 50 mA or less 55 mA or less Enclosure IP40 With manifold assembled Operating temperature range 10 to 50 o C Max surrounding air tempe...

Страница 31: ...4 Bit 5 Bit 6 Bit 7 Input signal assignment EX600 DX D Connector number 0 1 2 3 4 5 6 7 Connector position Pin 2 Bit 1 Bit 3 Bit 5 Bit 7 Bit 9 Bit 11 Bit 13 Bit 15 Input signal Pin 4 Bit 0 Bit 2 Bit...

Страница 32: ...ut signal assignment EX600 DX F Group 0 1 2 3 4 5 6 7 Terminal position Pin 2 Bit 0 Bit 2 Bit 4 Bit 6 Bit 8 Bit 10 Bit 12 Bit 14 Input signal Pin 3 Bit 1 Bit 3 Bit 5 Bit 7 Bit 9 Bit 11 Bit 13 Bit 15 D...

Страница 33: ...32 No EX OMN0036 EX600 DX C EX600 DX D...

Страница 34: ...33 No EX OMN0036 EX600 DX E EX600 DX F...

Страница 35: ...16 outputs P PNP F Spring type terminals 32 pin 16 outputs N NPN An M12 connector 4 pin can also be connected Names and Functions of Product EX600 DY B No Description Function 1 Status display LED Di...

Страница 36: ...C 5 Joint bracket Bracket for joining to adjacent units 6 Unit connector Plug Transmits signals and power supplies to adjacent units EX600 DY F No Description Function 1 Status display LED Displays th...

Страница 37: ...also be connected Circuit diagram EX600 DYPB EX600 DYNB Precautions for handling Be sure to fit a seal cap on any unused connectors Proper use of the seal cap enables the enclosure to achieve IP67 spe...

Страница 38: ...utput 0 2 Output 2 3 Output 4 4 Output 6 5 Output 8 6 Output 10 7 Output 12 8 Output 14 9 NC 10 NC 11 NC 12 NC 13 0 V Output 24 V Output 14 Output 1 15 Output 3 16 Output 5 17 Output 7 18 Output 9 19...

Страница 39: ...0 V Output 24 V Output 2 Output 8 3 0 V Output 24 V Output 4 4 Output 9 1 0 V Output 24 V Output 2 Output 10 3 0 V Output 24 V Output 5 4 Output 11 1 0 V Output 24 V Output 2 Output 12 3 0 V Output 24...

Страница 40: ...the following points when using the open circuit detection This function detects open circuit only when the output is OFF Therefore if output is turned ON open circuit can not be detected Refer to th...

Страница 41: ...rol and input or the output device is OFF Green LED is ON The output device is ON Red LED is ON The output device has a short circuit Red LED is flashing Either of the following conditions The output...

Страница 42: ...owing conditions The output device ON OFF count has exceeded the set value Each of output 0 to 15 The output device is open circuit Each of output 0 to 15 0 to 15 LEDs are OFF The output device is OFF...

Страница 43: ...mbled Operating temperature range 10 to 50 o C Max surrounding air temperature rating 50 o C 3 Storage temperature range 20 to 60 o C Operating humidity range 35 to 85 RH No condensation Withstand vol...

Страница 44: ...r 1 2 3 4 5 6 7 8 Signal name Output 0 Output 2 Output 4 Output 6 Output 8 Output 10 Output 12 Output 14 Output signal Bit 0 Bit 2 Bit 4 Bit 6 Bit 8 Bit 10 Bit 12 Bit 14 Pin number 14 15 16 17 18 19 2...

Страница 45: ...44 No EX OMN0036 Dimensions EX600 DY B EX600 DY E...

Страница 46: ...45 No EX OMN0036 EX600 DY F...

Страница 47: ...Spring type terminals 32 pin 8 inputs 8 outputs P PNP N NPN Names and Functions of Product EX600 DM E No Description Function 1 Status display LED Displays the status of the unit 2 Connector I O Conne...

Страница 48: ...lay LED Displays the status of the unit 2 Connector I O Connector for input and output devices 3 Marker groove Groove to mount a marker 4 Joint bracket Bracket for joining to adjacent units 5 Unit con...

Страница 49: ...E EX600 DMNE 1 Input 0 2 Input 1 3 Input 2 4 Input 3 5 Input 4 6 Input 5 7 Input 6 8 Input 7 9 24 V Control and input 10 24 V Control and input 11 0 V Control and input 12 0 V Control and input 13 FE...

Страница 50: ...the following points when using the open circuit detection This function detects open circuit only when the output is OFF Therefore if output is turned ON open circuit can not be detected Refer to th...

Страница 51: ...d input X1 1 24 V Control and input X2 2 Input 4 3 Input 5 2 4 0 V Control and input X2 1 24 V Control and input X3 2 Input 6 3 Input 7 3 4 0 V Control and input X3 1 0 V Output 24 V Output 2 Output 0...

Страница 52: ...the following points when using the open circuit detection This function detects open circuit only when the output is OFF Therefore if output is turned ON open circuit can not be detected Refer to th...

Страница 53: ...as a short circuit Each of input 0 to 7 Red ST O LED is ON The output device has a short circuit Each of output 0 to 7 Red ST I LED is flashing The input device ON OFF count has exceeded the set value...

Страница 54: ...t 0 to 7 Input left 0 to 7 green LEDs are ON The input device is ON Each LED display number corresponds to input 0 to 7 Output right 0 to 7 green LEDs are ON The output device is ON Each LED display n...

Страница 55: ...load current 0 5 A output 2 A unit Output specifications Protective function Short circuit protection Acceptable electric wire 0 08 to 1 5 mm 2 AWG 16 to 28 Current consumption 50 mA or less 60 mA or...

Страница 56: ...Input 6 Input 7 Input signal Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Pin number 14 15 16 17 18 19 20 21 Signal name Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Out...

Страница 57: ...56 No EX OMN0036 Dimensions EX600 DM E EX600 DM F...

Страница 58: ...ric wiring Connect properly if the connection is loose Seal cap Tighten properly if the connection is loose Thread for mounting and installation If the thread is loose re tighten it to the specified t...

Страница 59: ...ocol used Parameter Setting Refer to the SI unit Operation Manual of protocol used I O Map Refer to the SI unit Operation Manual of protocol used Diagnostic Refer to the SI unit Operation Manual of pr...

Страница 60: ...0 DX B EX600 DX C EX600 DX D EX600 DX E EX600 DX F EX600 DY B EX600 DY E EX600 DY F EX600 DM E Digital unit EX600 DM F EX600 AXA EX600 AYA Analog unit EX600 AMB EX600 HT1 H T EX600 HT1A H T EX600 HT1...

Страница 61: ...No EX OMN0036 Revision history Note Specifications are subject to change without prior notice and any obligation on the part of the manufacturer 2010 SMC Corporation All Rights Reserved...

Отзывы: