Switch setting
1. Setting of Address
•
UNIT STATUS
•
HOLD/CLR
•
HW/SW mode (SW1)
Setting of address is performed with SW1.
•
Address setting (Switch No.1 to 7)
All setting are turned OFF at shipment and the Address is set to 0.
Make sure to set the Address within the range of 0 to 125.
ADDRESS
64(No.1)
32(No.2)
16(No.3)
8(No.4)
4(No.5)
2(No.6)
1(No.7)
0
OFF OFF OFF OFF OFF OFF OFF
1
OFF OFF OFF OFF OFF OFF
ON
2
OFF OFF OFF OFF OFF
ON
OFF
3
OFF OFF OFF OFF OFF
ON ON
4
OFF OFF OFF OFF
ON
OFF OFF
: :
:
:
:
:
:
:
24 OFF
OFF
ON ON
OFF OFF OFF
25 OFF
OFF
ON ON
OFF OFF
ON
:
:
:
:
:
:
:
:
125
ON ON ON ON ON
OFF
ON
126
ON ON ON ON ON ON
OFF
127
ON ON ON ON ON ON ON
∗
: Setting of 126 and 127 are invalid.
•
UNIT STATUS setting (Switch No.8)
The setting is as follows.
Refer to page 23 for the memory map of GW status information.
At the time of shipment from the factory, the switch is set to off and the GW unit status information is not
sent to master side as an input data.
UNIT STATUS
No.8
Function
OFF
OFF
The GW unit status information is not sent to master side as an input data.
ON ON
The GW unit status information is sent to master side as an input data.
∗
: If the address setting is turned on, an input setting for PLC is required.
Refer to page 24 for the details of diagnosis information.
•
HOLD/CLR setting (Switch No.9)
The setting is as follows.
The setting at shipment is turned OFF, set to CLR.
HOLD/CLR
No.9
Function
CLR
OFF
Output is cleared when an communication error occurs.
HOLD
ON
Output is held when an communication error occurs.
∗
: HOLD/CLR setting is made available per one point by parameter setting.
Refer to page 29 for detail.
NOTE
1. Open the cover, and set DIP switch with a flat blade driver, etc.
2. Make sure that switch setting is performed with power supply turned off.
3. Be sure to perform this setting of the switch before use.