HRX-OM-R016
Chapter 5 Display and setting of various functions
HRS Series
5.16
Alarm customize function
5-41
Changing of circulating fluid discharge pressure drop
Setting and checking
16.
Press the [SEL] key once.
The set screen of changing of circulating fluid discharge pressure drop is displayed on
the digital display.
17.
Select changing of circulating fluid discharge pressure dro from the table below with [
▲]
key or [
▼] key, and confirm by pressing “SEL”.
Table 5.16-10
List of set value
Set value
Explanation
Initial value
(Default setting)
This alarm signal is not detected.
Operation continues when this alarm signal is
generated.
○
Operation is stopped when this alarm signal is
generated.
Detection temperature for circulating fluid discharge pressure drop
Setting and checking
18.
Press the [SEL] key once.
The set screen of detection temperature for circulating fluid discharge pressure drop is
displayed on the digital display.
19.
Select detection temperature for circulating fluid discharge pressure drop from the table
below with [
▲] key or [▼] key, and confirm by pressing “SEL”.
Table 5.16-11
List of set value
Set value
Explanation
Initial value
(Default setting)
Setting/checking are not available if the setting of
the circulating fluid discharge temperature drop is
OFF.
MPa
to
Sets detection temperature for circulating fluid
discharge pressure drop.
・
Option -T, -MT (100V)
Set range: 0.05 to 0.55MPa (7 to 80PSI)
・
Option -T (200V)
Set range: 0.05 to 0.70MPa (7 to 102PSI)
・
Option -MT (200V)
Set range: 0.05 to 0.60MPa (7 to 87PSI)
Pressure unit is MPa: Setting unit is 0.01MPa
Pressure unit is PSI: Setting unit is 1PSI
PSI
to
PV
SV
PV
SV
Содержание HRS030-A-20 series
Страница 8: ...HRX OM R016 Contents HRS Series ...
Страница 122: ...HRX OM R016 Chapter 5 Display and setting of various functions 5 19 Communication function HRS Series 5 70 ...
Страница 128: ...HRX OM R016 Chapter 6 Option Optional Accessories 6 5 Optional Accessories Drain pan set HRS Series 6 6 ...
Страница 144: ...HRX OM R016 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS Series 8 10 ...
Страница 156: ...HRX OM R016 Chapter 9 Documents 9 10 Daily Check Sheet HRS Series 9 12 ...
Страница 159: ......