HRX-OM-R016
Chapter 4 Starting the Product
4.3
Preparation of circulating fluid
HRS Series
4-4
2.
Press the [RESET] key ([▼] and [▲] keys simultaneously) to stop the alarm buzzer.
Fig. 4-5 Alarm receipt
3.
Open the tank lid and supply
the circulating fluid up to the “H” mark on the tank.
Fig. 4-6 Filling of Circulating Fluid
Flash
Press together
Tank lid
Filling of Circulating Fluid
Liquid
level
ON
Be sure to reset the alarm on the operation display panel of the alarm.
Alarm reset
is not accepted from any screen except the alarm display menu. Refer to 5.2.1 Key
operations.
Supply the circulatin
g fluid up to the “H” mark on the tank.
Operation will stop when the fluid level falls
lower than “L”.