HRX-OM-R016
Chapter 9 Documents
HRS Series
9.1 Specifications List
9-1
Chapter 9 Documents
9.1 Specifications List
9.1.1
Product specification
Table 9-1 Specifications List [HRS030-
-20-
(
BJMT
)
]
Model
HRS030-A
-20-
(
BJMT
)
HRS030-W
-20-
(
BJMT
)
Cooling method
Air-Cooled refrigerated type
Water-Cooled refrigerated type
Refrigerant
R407C(HFC)
Quantity of refrigerant
kg
0.57
0.5
Control method
PID control
Ambient temperature and
humidity
2
Temperature: 5 to 40
o
C
、
Humidity: 30 to 70%
Ci
rcu
la
tin
g
f
lui
d
sy
ste
m
Circulating fluid
3
Tap water, Ethylene glycol aqueous solution 15%
5
Operating temperature
range
2
o
C
5 to 40
Cooling capacity
4
(50/60Hz)
W
2600/3200
Temperature stability
6
o
C
±0.1
Pump capacity
7
(50/60Hz)
MPa
0.13(at 7L/min)/0.18(at 7L/min)
For option -T: 0.44(at 10L/min)/0.40(at 14L/min)
For option -MT: 0.32(at 10L/min)/0.32(at 14L/min)
Rated fiow
8
(50/60Hz)
L/min
7/7 For option -T, -MT
:
10/14
Tank capacity
L
Approx. 5
Port size
Rc1/2
Wetted material
Stainless steel, Copper brazing (Heat exchanger)
15
, Bronze
15
Brass
15,
SIC, Aluminum oxide ceramic, Carbon, PP, PE, POM, FKM, EPDM, PVC
F
a
cil
it
y wa
te
r
out
le
t
sys
te
m
1
Temperature range
o
C
-
5 to 40
Pressure range
MPa
-
0.3 to 0.5
Required flow
13
L/min
-
15
Facility water pressure
differential
MPa
-
0.3 more
Port size
Rc3/8
Wetted material
Stainless steel, Copper brazing, Bronze, Synthetic rubber
A
u
to
m
a
tic
flu
id
fill
in
g
14
Feed water pressure
range
MPa
0.2 to 0.5
Feed water temperature
range
o
C
5 to 40
Feed water capacity
L/min
Approx.1
Automatic fluid filling Port size
Rc3/8
Over flow port Port size
Rc3/4
E
lect
ric
syst
e
m
Power supply
1-phase AC200 to 230V 50/60Hz.
Allowable voltage range ±10%
Circuit protector
17
A
10 (For option
-T
,
-MT : 15
)
Applicable earth leakage
breaker capacity
9
A
10 (For option
-T
,
-MT : 15
)
Rated operating current
4
(50/60Hz)
A
5.2/6.0
For option
-T
,
-MT : 6.2/7.6
Rated power
consumption
4
(50/60Hz)
kVA
1.0/1.2
For option
-T
,
-MT : 1.2/1.5
Noise level
10
(50/60Hz)
dB
62/65
Dimensions
11
mm
W377xD500xH660 (W14.8XD19.7xH26.0[Inch])
Accessory
Fitting (for drain port) 1pc.
16
, Sequence I/O command
signal connector 1pc., Power supply connector 1pc., Operation manual (Installatio
・
Operation ) 1pc,
Quick manual (with a clear cover) 1pc., Alarm code list label 1pc.
Weight
12
kg
47
46
1
For water -cooled type.
2
Use the product in conditions where freezing will not occur.
Consult with SMC if using in a season or region where the ambient temperature will fall below zero.
3
If tap water is used, use water which satisfies the standard of The Japan Refregeration And Air Conditioning Industry Association (JRA GL-02-1994/Cooling water system -
circulation type - make-up water)
4
(1)Operating ambient temp.: 25
o
C, (2)Circulating fluid temp.: 20
o
C, (3)Circulating fluid rated flow, (4)Criculating fluid : Tap water,(5)Facility water temp.: 25
o
C.
The cooling capacity will be reduced by 300W when option
T and MT [High head pump] are selected.
5
Use a 15% ethylene glycol aqueous solution if operating in a place where the circulating fluid temp. is lower than 10
o
C.
6
Outlet temp. when the circulating fluid flow is rated flow, and the circulating fluid outlet and the return are directly connected. Installation environment and power supply are
within specification range and stable.
7
The capacity at the thermo-chiller outlet when the circulating fluid temp. is 20
o
C.
8
Fluid flow to maintain the cooling capacity and the temperature stability.
The specification of the coolong capacity and the temperature stability may not be satisfied if the flow rate is lower than the rated flow.
9 To be prepared by the customer. Use an earth leakage breaker with sensitivity of 30mA/200V in power supply specification..
10 Front 1m/Height 1m/Static with no load. See note 4 for other conditions.
11 Dimension between panels. Projection is not included.
12 Weight when the circulating fluid
and facility water (for water-cooled type) is not included.
The weight will increase by 1kg when option
J [Automatic fluid filling] is selected. The weight will increase by 6kg when option
T and MT [High head pump] are selected.
13 There is required flow when adding load described on cooling capacity in case of note 4 conditions.
14
For option
J [Automatic fluid filling port].
15
Copper, bronze and brass are not included when option
M [DI water piping] is selected
16
This fitting is not included when option
T and MT [High head pump]
are selected.
17 If option
“Earth leakage breaker type” is selected, the earth leakage breaker is used instead of the circuit protector.
Содержание HRS030-A-20 series
Страница 8: ...HRX OM R016 Contents HRS Series ...
Страница 122: ...HRX OM R016 Chapter 5 Display and setting of various functions 5 19 Communication function HRS Series 5 70 ...
Страница 128: ...HRX OM R016 Chapter 6 Option Optional Accessories 6 5 Optional Accessories Drain pan set HRS Series 6 6 ...
Страница 144: ...HRX OM R016 Chapter 8 Control Inspection and Cleaning 8 4 Stop for a Long Time HRS Series 8 10 ...
Страница 156: ...HRX OM R016 Chapter 9 Documents 9 10 Daily Check Sheet HRS Series 9 12 ...
Страница 159: ......