System Components 

 

FR-8000 Master Display Unit (MDU) 

 
Provides the following functions 

 

12/24 volt.  

 

Early detection and warning of engine room fire.  

 

Full machinery shutdown management for up to six devices (see FEC-6). 

 

Comprehensive fault monitoring.  

 

Cylinder pressure monitoring (see FEC-6). 

 

  Latched display for up to 8 Alarms 

o

  All names are user programmable 

o

  Network communication fault  

o

  Visual alarm with tone  

 

 

FR-100 Input/Output Unit (IOU) 

 

The FR-100 is a controller, which provides 8 Zone Inputs for Smoke Sensors and 1 
Output Relay.  
 

  Each Input requires 4K7 end of line resistor for supervised line 

 

Minimum fault sense current = 8mA

 

         

 

Output Relay’s

 

 

o

 

10 A  resistive @ 24VDC

 

 

o

 

Relay 1 & Relay 2 close on Fire detection

 

 

o

 

Relay 1 opens when alarm is muted

 

 

o

 

Relay 2 opens when all zones are OK

 

 

 

FEC-1 Engine Relay Controller 

 

The FEC-1 has one relay.  

 

o

 

Output Relay 1  = 3 amp inductive 

 

 

 

FEC-6 Engine Relay Controller 

 

 

The FEC-6 has six relays.  

 

o

 

Output Relay 1 to 4 = 10 A  resistive @ 24VDC

 

 

o

 

Output Relay 5 & 6 = 1 A  resistive @ 30VDC

 

 

 

Pyro-5 Pyrogen interface module 

 

Monitor and release up 

to 5 Pyrogen extinguisher bottle’s  

 

Содержание FR-8000

Страница 1: ...SMARTSWITCH FR 8000 Fire Alarm Monitor Installation Manual...

Страница 2: ...e Room Layout 7 Wiring Diagram for FR 8000 8 Wiring Diagram for FR 100 9 Connection Diagram for FEC 6 FEC 1 10 Installation Electrical Specifications 11 Mounting Instructions 12 System Overview 13 Rel...

Страница 3: ...ne environment using proven techniques and materials which will ensure a long life at sea The FR 8000 provides features found only in expensive computer based systems on mega yachts but does so for a...

Страница 4: ...s a controller which provides 8 Zone Inputs for Smoke Sensors and 1 Output Relay Each Input requires 4K7 end of line resistor for supervised line Minimum fault sense current 8mA Output Relay s o 10 A...

Страница 5: ...Wiring Block Diagram FR 8000 Master Display Unit MDU Optional Sensors Sensor NOTE Sensors must have 4K7 ohm end of line resistor fitted Battery negative Battery positive Relay 1 FR 100 IOU Aux battery...

Страница 6: ...OL FR 100 IOU Zone Zone Wiring for the extinguisher trigger cupboard door 1k ohm 4K7 ohm Normally open switch Switch closes when door is opened FR 100 IOU End of line resistor Note Detector manufactur...

Страница 7: ...le Sensors Per Zone Note Detector manufactures use different terminal designators E g L1 L2 L3 OR Com In Out 4K7 Ohm end of line resistor EOL Zone Zone L1 or In or 1 L1 or In or 1 L or Com or 6 L or C...

Страница 8: ...ut Unit Relay 1 Relay 2 Sensor Gas cylinder release door switch FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure switch Optional FEC 6 or FEC 1 FEC 1 Relay...

Страница 9: ...FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure switch FEC 6 Engine Relay Unit Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Gas cylinder pressure swit...

Страница 10: ...s Red Vdc Black GND Blue Coms White Coms Back View White Blue Black Red Power and Comms Wiring Connections FR 8000 FEC 6 Optional FEC 6 Optional 4 Core Cable Supplying Vdc GND Coms Coms Aux Battery Ma...

Страница 11: ...e Aux Battery terminal Aux Battery To Main Battery To Main Battery Main Battery Aux Battery Aux Battery Main Battery D1 Zone 5 Zone 5 Zone 6 Zone 6 Zone 7 Zone 7 Zone 8 Zone 8 Zone 1 Zone 1 Zone 2 Zon...

Страница 12: ...Com Relay 3 N C N O N O Com Com N C Relay 2 Relay 1 N O Com Relay 5 N C Com N O N C Relay 6 Com Com Input 1 Input 2 Input 3 Input 4 Input Common Links MUST be installed SmartSwitch Address FEC 6 www...

Страница 13: ...wer Electrical Specifications FR 100 Supply Voltage 10 to 30 Volts DC Auto Sensing Quiescent Curent 30 mA Min fault sense current 8mA Relay 1 10 A resistive 24VDC Relay 2 10 A resistive 24VDC Electric...

Страница 14: ...tighten the screws until the template tool can just slip on and off the screws ensure the tool in not too loose Drill the bottom hole to 12 mm cable hole Place the Display Unit keyholes over the two...

Страница 15: ...ls In manual mode it will ask you to press the enter key to start this process An extinguisher trigger cupboard door or doors may be connected to a Sensor Input Unit FR 100 This input is fully monitor...

Страница 16: ...has elapsed Relay 4 will activate Example If the solenoid on the extinguisher bottles is connected Relay 4 and the stop time is set to 30 seconds this would give a 30 second window for the fans and en...

Страница 17: ...key to accept Step 3 Selecting Creating Zone Name s The display will now show Use the Select Up or Down key to scroll through the pre named zone names Once you have found the one required press the E...

Страница 18: ...rogram a zone Think of it as each zone has a memory look up position and in the memory position is a name that the zone uses Rotary Switch 2 Zone Zone Choose one Zone name designation from list on rig...

Страница 19: ...s to the Zone you wish to remove Once the Input number has been selected press the Ent key to accept EXTINGUISHER DOOR If the vessel is fitted with an extinguisher cupboard holding the extinguisher tr...

Страница 20: ...needs to be associated with either the Port or Stb FEC 6 engine controller If there is only a FEC 1 fitted then you can choose either Port or Stb as either will work The display will now show Use the...

Страница 21: ...shut down the fans and engine the system will automatically do it If manual is selected the system will ask you See Relays page 14 EXTINGUISHER SWITCH INPUT The extinguisher bottle pressure switch may...

Страница 22: ...g mode The FR 8000 is now ready for use Alarms Should a Smoke Sensor detect smoke or fire the text FIRE will flash on the display The audible alarm will sound and both Relay 1 and Relay 2 in the FR 10...

Страница 23: ...ng or other deterioration more severe than that resulting from a similar test on passivated AISI Type 304 stainless steel Locations requiring an exceptional degree of protection means a location expos...

Страница 24: ...design and Intellectual Property is owned by Penguin Electronics Ltd Po Box 272 Waikanae New Zealand Ph 0064 4 293 4201 Fax 0064 4 293 4201 Mobile 0064 274 919 805 Email info smartswitch co nz Web ww...

Отзывы: