18
Use the Select Up or Down key to scroll through the pre-named zone names. Once you have
found the one required press the Ent key.
If you would like to create your own name press the Mute key. Use the Select up or down key
to scroll through the alphabet and the Dim up or down keys to change to the next character.
When finished press the Ent key.
You now need to associate the door switch with a relay controller (FEC-6 or FEC-1).
If a FEC-6 is installed Relay 5 & 6 will activate when the extinguisher door is opened. Relay 6
will stay activated until the door is closed, Relay 5 will deactivate when the Mute key is
pressed on the FR-8000 (MDU). If a FEC-1 is fitted the Relay will activate when the door is
open. The zone needs to be associated with either the Port or Stb (FEC-6) engine controller.
If there is only a FEC-1 fitted then you can choose either Port or Stb, as either will work.
The display will now show:
Use the Select Up or Down key to scroll between Port and Stb, (if the vessel is single engine
room then just select Port) and press the Ent key to accept.
ENGINE CONTROLLER:
If a FEC-6 or FEC-1 is installed, scroll down to ENGINE CONTROLLER and press the Ent
key.
You will now see a new Menu. This is the Engine Room Controller Set-Up Menu and is used to
associate a zone with the FEC-6 engine room controller
The system will now display:
SET THE ENGINE BOX
ASSOCATED WITH ZONE
Select Eng I/O Port
Push MUTE to Exit
Push ENT to Enter
SET-UP MENU
PROGRAM ZONE
REMOVE ZONE
EXTINGUISHER DOOR
ENGINE CONTROLLER
ERASE I/O BOX
EXIT MENU
ENGINE CONTROL MENU
SET ZONE
REMOVE ZONE
ENG STOP TIME
AUTO / MANUAL
EXTINGUISHER INPUT
EXIT MENU