SMARTSCAN C4 compact ME Series Скачать руководство пользователя страница 24

 

Safety Light Curtain – C4 compact ME Series 

 

Installation Guide

 

 

File Number: CD1011               

page 24                                                                            Date: 12 April, 2017

 

Figure J – Test and Maintenance 

Testing the safety light curtain with the test piece 

 

The test procedure should be carried 

out frequently as indicated by the risk 

assessment for the particular 

installation. 

 

A test must be carried out at the initial 

installation and prior to the machine 

start-up. 

 

Smartscan TW Ltd recommends the 

test should be carried out daily. 

 

Any changes to the configuration of 

the safety light curtain must be 

followed by testing to check the 

system is still working correctly. 

 

Regular function checking of the 

safety light curtain as well as at initial 

installation is required as part of the 

test and maintenance process. 

 

The operating instructions for the 

safety light curtain and machine must 

be made available for the operator 

and those responsible for installation, 

maintenance and safety control at all 

times. 

 

To test the safety light curtain power it up and activate the output switching circuits (OSSDs) to 

an ON condition. 

 

Insert a test piece of appropriate size into the light curtain detection zone, at the bottom, 150mm 

from the transmitter unit.    At this point the output switches will turn OFF.    Sweep the test piece 

Содержание C4 compact ME Series

Страница 1: ...C4 compact ME SERIES SAFETY LIGHT CURTAINS INSTALLATION GUIDE MACHINERY SAFETY SYSTEMS...

Страница 2: ...duct The Installation Sheet and Installation Guide can be downloaded from our web site at www smartscan com tw The C4 compact ME series Safety Light Curtain Installation Guide CD1011 is subject to cha...

Страница 3: ...Supply 16 Automatic Reset 16 External Device Monitoring EDM 17 Safety Outputs OSSD1 and OSSD2 17 Communication Link 18 Figure H Identification Labels 19 Figure I Status and Diagnostic Indication 20 R...

Страница 4: ...g Remove all packaging material and retain it Locate and keep the delivery note Inspect all items for transit damage Match goods supplied to those specified on the delivery note Keep the Installation...

Страница 5: ...d at the ends of the safety light curtain as shown above The mounting bracket may be fixed at 90 degrees with a 5 adjustment Use 4mm bolts for mounting and ensure they are fixed so as to prevent any m...

Страница 6: ...safety light curtain s overall length including mounting brackets fixing centres and detection zone width The detection zone width DZ DZ2 or protected height is needed to select the appropriate lengt...

Страница 7: ...C and 50 C Vibration Frequency 55Hz Max Movement 0 35mm Do not use equipment in explosive atmospheres contact the manufacturer for further advice Detection Zone width DZ The detection zone width or p...

Страница 8: ...tain is capable of satisfying the range requirement for the particular application it is being used for Reset Location Reset devices must be located such that the danger area can be seen to be clear o...

Страница 9: ...is not directed towards the Perspex window of the receiver unit RX Extraneous sources would include infrared sensors infrared remote controls scanning systems or sunlight 3 Ensure the mounting positio...

Страница 10: ...eing guarded 4 Ensure the light curtain transmitter TX and receiver RX units are mounted accurately in line with each other and are both perpendicular and parallel to each other within the parameters...

Страница 11: ...Safety Light Curtain C4 compact ME Series Installation Guide File Number CD1011 page 11 Date 12 April 2017 Figure F Electrical Connections Reset Mode Manual Latched...

Страница 12: ...perator first checking that the dangerous area is clear of personnel and therefore safe The reset switch must also be located so that the operator cannot reset the light curtain from inside the danger...

Страница 13: ...head should be connected via a normally closed NC contact of the external Final Switching Device FSD being monitored The other side of the contact is connected to 24V DC If the EDM is not being used t...

Страница 14: ...via DATA Link The Violet wire from the Transmitter TX head cable must be connected to the Violet wire from the Receiver RX head cable Warning The Data wires are communication links and have DATA Link...

Страница 15: ...Safety Light Curtain C4 compact ME Series Installation Guide File Number CD1011 page 15 Date 12 April 2017 Figure G Electrical Connections Auto Reset Mode...

Страница 16: ...safety outputs OSSDs Removing the blockage from the sensing field of the light curtain will re activate and turn on the safety outputs OSSDs The configuration of the safety light curtain in the auto...

Страница 17: ...itching device FSD being monitored The other side of the contact s is connected to 24V DC If the EDM is not being used the Green wire must be connected to a permanent 24V DC L The bottom yellow LED in...

Страница 18: ...via DATA Link The Violet wire from the Transmitter TX head cable must be connected to the Violet wire from the Receiver RX head cable Warning The Data wires are communication links and have DATA Link...

Страница 19: ...Series Installation Guide File Number CD1011 page 19 Date 12 April 2017 Figure H Identification Labels Examples are shown below of the identification labels that are affixed to the bottom of the tran...

Страница 20: ...light curtain and in fault diagnosis Receiver RX Status Indicators GREEN LED on Light curtain safety reset has been initiated and the OSSDs are in the on state only when the light curtain detection z...

Страница 21: ...st The C4 compact ME series signal strength is monitored from the bottom block of 3 beams those nearest the cable entry Fault Diagnosis The display panel also provides 6 different error codes E0 E1 E2...

Страница 22: ...upside down e g with the connection cables at the top furthest away from the floor rather than the bottom nearest the floor This allows the user to read the TX display even when the light curtain is...

Страница 23: ...tors Block Beam blocked The Block LED is a Red indicator Clear Light curtain active The Green Indicators help the operator to see the current operating status of the safety light curtain Green lights...

Страница 24: ...ain must be followed by testing to check the system is still working correctly Regular function checking of the safety light curtain as well as at initial installation is required as part of the test...

Страница 25: ...utput switches should only turn OFF as the test piece totally obscures each beam in the light curtain Ensure that while the test piece is obscuring each beam the output switches are OFF Maintenance Th...

Страница 26: ...lation Sheet provided paying particular attention to the information provided in Fig E o Refer to Fig J for test and maintenance procedures o Every 24 hours carry out tests as indicated in Fig J o Eve...

Страница 27: ...ure If a fault occurs that cannot be resolved or the equipment is damaged return the equipment to the nearest Smartscan distributor or Smartscan TW Ltd Indicate the nature of the fault and the symptom...

Страница 28: ...el List Fig M shows the C4 compact ME series safety light curtain model numbers with their corresponding number of Infrared beams detection zone width DZ DZ2 fixing centres CTR CTR2 overall length L2...

Страница 29: ...ad zone C4 series Standard dead zone Note Main unit M and extender unit E be connected by cables Depend on customer s order We will give a total model No and note separately its M E unit The total len...

Страница 30: ...ngth C mm Assembly Length D mm C4B 6M 6 180 183 218 246 C4B 12M 12 330 333 368 396 C4B 18M 18 480 483 518 546 C4B 24M 24 630 633 668 696 C4B 30M 30 780 783 818 846 C4B 36M 36 930 933 968 996 C4B 42M 4...

Страница 31: ...m Assembly Length D mm C4B 6LM 6 190 183 218 246 C4B 12LM 12 340 333 368 396 C4B 18LM 18 490 483 518 546 C4B 24LM 24 640 633 668 696 C4B 30LM 30 790 783 818 846 C4B 36LM 36 940 933 968 996 C4B 42LM 42...

Страница 32: ...ngth C mm Assembly Length D mm C4B 6E 6 180 172 207 235 C4B 12E 12 330 322 357 385 C4B 18E 18 480 472 507 535 C4B 24E 24 630 622 657 685 C4B 30E 30 780 772 807 835 C4B 36E 36 930 922 957 985 C4B 42E 4...

Страница 33: ...m Assembly Length D mm C4B 6LE 6 190 172 207 235 C4B 12LE 12 340 322 357 385 C4B 18LE 18 490 472 507 535 C4B 24LE 24 640 622 657 685 C4B 30LE 30 790 772 807 835 C4B 36LE 36 940 922 957 985 C4B 42LE 42...

Страница 34: ...odel Beams Protection Zone K mm Overall Length B mm Install Length C mm Assembly Length D mm C4A 4M 4 205 188 223 251 C4A 8M 8 365 348 383 411 C4A 12M 12 525 508 543 571 C4A 16M 16 685 668 703 731 C4A...

Страница 35: ...eams Protection Zone K mm Overall Length B mm Install Length C mm Assembly Length D mm C4A 4LM 4 210 188 223 251 C4A 8LM 8 370 348 383 411 C4A 12LM 12 530 508 543 571 C4A 16LM 16 690 668 703 731 C4A 2...

Страница 36: ...odel Beams Protection Zone K mm Overall Length B mm Install Length C mm Assembly Length D mm C4A 4E 4 205 182 217 245 C4A 8E 8 365 342 377 405 C4A 12E 12 525 502 537 565 C4A 16E 16 685 662 697 725 C4A...

Страница 37: ...eams Protection Zone K mm Overall Length B mm Install Length C mm Assembly Length D mm C4A 4LE 4 210 182 217 245 C4A 8LE 8 370 342 377 405 C4A 12LE 12 530 502 537 565 C4A 16LE 16 690 662 697 725 C4A 2...

Страница 38: ...Safety Light Curtain C4 compact ME Series Installation Guide File Number CD1011 page 38 Date 12 April 2017 Figure N Declaration of Conformity...

Страница 39: ...Safety Light Curtain C4 compact ME Series Installation Guide File Number CD1011 page 39 Date 12 April 2017 Figure O Glossary of Words and Language Translation...

Страница 40: ...ng machine application must be complied with The safety light curtain is only one element in the overall machine safety circuit the whole machine safety control circuit must be a fail safe design The...

Страница 41: ...s a certified quality assurance system in compliance with ISO 9001 2008 Certificate number 79Q13722 Products Smartscan safety light curtains are developed and manufactured in compliance with the Europ...

Страница 42: ...eduction in optical efficiency reducing the effective range A guide to the practicality of using mirrors is given below Range of the light curtain Maximum range through 1 mirror Maximum range through...

Страница 43: ...the Perspex window of the transmitter unit can be seen reflected in the mirror 6 If the light curtain is scanning over a long range it may be difficult to see the reflection of the transmitter units P...

Страница 44: ...ft and to the right until the entire length of the transmitter unit is reflected through both the first mirror and the second mirror If difficulties are experienced in seeing the reflection of the tra...

Страница 45: ...ed energy from the transmitter unit is being reflected through the mirror s to the corresponding receiver unit Alignment of the light curtain using mirrors Note The mirror length must be a minimum of...

Страница 46: ...rs RX Green LED on OSSDs on Yellow LED EDM on Red LED on OSSDs off Yellow LED on Infrared beams aligned Top Yellow LED on Infrared beams aligned No signals quickly blinking yellow Not alignment slowly...

Страница 47: ...d Per Hour 1 66958E 09 T1 Life Span in Years 20 Years MTTFd Years 100 Years or more DC Diagnostic Coverage 99 Warranty One Year OUTPUTS Safety Outputs OSSD1 OSSD2 2 x electronic switches PNP each rate...

Страница 48: ...Safety Light Curtain C4 compact ME Series Installation Guide File Number CD1011 page 48 Date 12 April 2017 Notes...