4.
The Command & Control Center will flash a fault when 250 hours have passed since
the previous filter change. After replacing the filter, this fault can be removed from
the Command & Control Center, and the filter run time can be reset by performing
the following steps:
Step a: Press Mode until
,
,
and
appear.
Step b: Hold Mode switch
down and press On/Off three
times in a row to clear the
fault.
Procedure will also work
in the Oil Filter Hours
Information display
Figure 30 - Filter Service Reset
a. Press the Mode button repeatedly until one of the screens shown in Figure 30
appears.
b. While holding the Mode button down, press and release the On/Off button three
times in succession, then release the Mode button. The Oil Filter Fault display
will be removed and replaced by another screen. The fault has been cleared and
the timer reset.
c. When the fault has been cleared, the system automatically enters purge mode
(Figure 13) to purge any entrapped air from the hydraulic lines per installation
Section 10. Turn off the main power breaker during purge (see Figure 12). While
purging, the system will not produce usable electrical power.