Smart Power Systems
®
A. C. MODULAR GENERATOR SYSTEM
Page 38 of 52
4.
The Command & Control Center will flash a fault when 250 hours have passed
since the previous filter change. After replacing the filter, this fault can be removed
from the Command & Control Center, and the filter run time can be reset by
performing the following steps:
Step a: Press Mode until
InF
,
0IL
,
and
FILt
appear.
Step b: Hold Mode switch
down and press On/Off three
times in a row to clear the
fault.
Procedure will also work
in the Oil Filter Hours
Information display
Figure 29
– Oil Filter Service Warning Display
a. Press the Mode switch repeatedly until one of the screens shown in
Error! R
eference source not found.
9 appears.
b. While holding the Mode switch down, press and release the On/Off switch three
times in succession, then release the Mode switch. The Oil Filter Fault display
will be removed and replaced by another screen. The fault has been cleared
and the timer reset.
c. When the fault has been cleared, the system automatically enters purge mode
(Figure 12) to purge any entrapped air from the hydraulic lines per installation
section 9. Turn off the main power breaker during purge (Mounted inside
generator enclosure as in Figure 10.) While purging, the system will not
produce usable electrical power.