background image

                         

 

HMU8-860 ATS Remote Monitoring Controller User Manual                                                  Page 41 of 50 

No. 

Item 

Description 

66

 

 

Load 4 Test Position Status  Load breaker 4 test position status input. 

67

 

 

Load 4 Breaker Trip 

Load breaker 4 trip fault input. 

68

 

 

Load 5 Close Status 

Load breaker 5 closed status input. 

69

 

 

Load  5  Work  Position 
Status 

Load breaker 5 work position status input. 

70

 

 

Load 5 Test Position Status  Load breaker 5 test position status input. 

71

 

 

Load 5 Breaker Trip 

Load breaker 5 trip fault input. 

72

 

 

Load 6 Close Status 

Load breaker 6 closed status input. 

73

 

 

Load  6  Work  Position 
Status 

Load breaker 6 work position status input. 

74

 

 

Load 6 Test Position Status  Load breaker 6 test position status input. 

75

 

 

Load 6 Breaker Trip 

Load breaker 6 trip fault input. 

76

 

 

Load 7 Close Status 

Load breaker 7 closed status input. 

77

 

 

Load  7  Work  Position 
Status 

Load breaker 7 work position status input. 

78

 

 

Load 7 Test Position Status  Load breaker 7 test position status input. 

79

 

 

Load 7 Breaker Trip 

Load breaker 7 trip fault input. 

80

 

 

Load 8 Close Status 

Load breaker 8 closed status input. 

81

 

 

Load  8  Work  Position 
Status 

Load breaker 8 work position status input. 

82

 

 

Load 8 Test Position Status  Load breaker 8 test position status input. 

83

 

 

Load 8 Breaker Trip 

Load breaker 8 trip fault input. 

84

 

 

Load 9 Close Status 

Load breaker 9 closed status input. 

85

 

 

Load  9  Work  Position 
Status 

Load breaker 9 work position status input. 

86

 

 

Load 9 Test Position Status  Load breaker 9 test position status input. 

87

 

 

Load 9 Breaker Trip 

Load breaker 9 trip fault input. 

88

 

 

Load 10 Close Status 

Load breaker 10 closed status input. 

89

 

 

Load  10  Work  Position 
Status 

Load breaker 10 work position status input. 

90

 

 

Load  10  Test  Position 
Status 

Load breaker 10 test position status input. 

91

 

 

Load 10 Breaker Trip 

Load breaker 10 trip fault input. 

92

 

 

Load 11 Close Status 

Load breaker 11 closed status input. 

93

 

 

Load  11  Work  Position 
Status 

Load breaker 11 work position status input. 

94

 

 

Load  11  Test  Position 
Status 

Load breaker 11 test position status input. 

95

 

 

Load 11 Breaker Trip 

Load breaker 11 trip fault input. 

96

 

 

Load 12 Close Status 

Load breaker 12 closed status input. 

97

 

 

Load  12  Work  Position 
Status 

Load breaker 12 work position status input. 

98

 

 

Load  12  Test  Position 
Status 

Load breaker 12 test position status input. 

Содержание HMU8-860

Страница 1: ...HMU8 860 ATS REMOTE MONITORING CONTROLLER USER MANUAL SMARTGEN ZHENGZHOU TECHNOLOGY CO LTD...

Страница 2: ...ncluding photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Applications for the copyright holder s written permission to reprodu...

Страница 3: ...struction NOTE Highlights an essential element of a procedure to ensure correctness CAUTION Indicates a procedure or practice which if not strictly observed could result in damage or destruction of eq...

Страница 4: ...R CONFIGURATION OF MONITORING MODULE 20 4 3 2 PARAMETER CONFIGURATION OF MASTER CONTROL MODULE 20 4 3 3 ADVANCED PARAMETER CONFIGURATION 21 5 WIRING 22 5 1 HUM8 860 MONIROTING MODULE REAR PANEL 22 5 2...

Страница 5: ...ller adopts high performance ARM chip large high resolution capacitive touch screen with Chinese and English display which can realize remote control data monitoring and parameter configuration of HAT...

Страница 6: ...and power factor of master control module Display S1 S2 accumulated active energy reactive energy close times auto transfer times mains failure transfer times of master control module Display current...

Страница 7: ...s 250m using Belden 9841 cable or equivalent Vibration Frequency 5Hz 8Hz Amplitude 7 5mm Range 8Hz 500Hz Fixed acceleration 2g IEC60068 2 6 Shock Acceleration 50g Pulse continuous time 11ms Waveform h...

Страница 8: ...iption Alarm Warning alarm slow flash 1 time per second Shutdown alarm fast flash 5 times per second No alarm extinguish Comm It is always illuminated when the communication between display module and...

Страница 9: ...ay Area Description Custom Description Character 1 Display HAT860 custome description character 1 Custom Description Character 2 Display HAT860 custome description character 2 Alarm Information Displa...

Страница 10: ...n manual mode press it can control ATS to open QS2 Close When the master control module is in manual mode press it can control QS2 to close Manual Mode Press it to transfer master control module to ma...

Страница 11: ...ts genset icon is shown in green and text indicates Genset Working when genset is in standby the icon is shown in gray and text indicates Genset Standby Fig 3 Genset Operation Interface Table 7 Key De...

Страница 12: ...with master control configuration each page can display up to 6 items and the maximum number of items is 24 Fig 4 Manual Operation Interface of Load Stepwise Switch Table 8 Key Description of Load St...

Страница 13: ...etailed Information Display Interface The detailed information interface displays S1 electric parameters includes phase voltage line voltage current phase sequence frequency information S2 electric pa...

Страница 14: ...e overcurrent action is set as trip and S1 takes load current is greater than the set value 6 S2 Load Overcurrent Trip When the overcurrent action is set as trip and S2 takes load current is greater t...

Страница 15: ...than the set value 2 S2 Load Overcurrent Overcurrent action is set as warning when S2 takes load current is greater than the set value 3 Forced Open Forced open non fire cutoff action is set as warni...

Страница 16: ...event records including the serial number total numbers of the current event the type of event the detailed contents of the event and the time when it happened By and keys up to 200 event records can...

Страница 17: ...output QS1 open output QS2 open output QS1 synchronous close QS2 synchronous close NEL1 trip NEL2 trip NEL3 trip Genset start S1 genset start S2 genset start Genset stop S1 genset stop S2 genset stop...

Страница 18: ...fault alarm S1 genset fault S2 genset fault S1 breaker trip alarm S2 breaker trip alarm Input 1 6 comm Failure fault Output 1 3 comm Failure fault Load switching failure Earth fault QTIE close failure...

Страница 19: ...this key to set the time and date of master control module Brightness Press this key to adjust the screen brightness of monitoring module adjusting range is 0 10 default is 6 and conduct lamp test ope...

Страница 20: ...as follows 1 Select parameters to be configured by the tree diagram 2 Set parameters to be changed in the right window Press the numeric keypad key when necessary to pop up the numeric keypad 3 After...

Страница 21: ...ation if communication fails and then returns to normal the monitoring module will re read and load the parameter configuration of the master control module NOTE3 The monitoring module cannot configur...

Страница 22: ...nd is grounded Short connect terminal 4 and 6 and connect 120 terminal resistor 5 CAN L 0 5mm2 6 CAN H 0 5mm2 7 PE1 Protective earth 8 RS485 1 Terminal match resistor 120 0 5mm2 Used for connecting ma...

Страница 23: ...sted shielding wire with 120 impedance whose single end is grounded Short connect terminal 20 and 22 and connect 120 terminal resistor 21 B 0 5mm2 22 A 0 5mm2 23 PE5 Protective earth NOTE1 Slave USB i...

Страница 24: ...Parity 4 Stop Bit 1 2 2 1 1 Bit 2 2 Bits RS485 2 Setting Reserved 1 Module Address 1 254 001 The module address of current RS485 interface is not used when communicating with the master control modul...

Страница 25: ...25 3 Subnet Mask 255 255 255 000 4 Gateway 192 168 010 001 5 DNS Address 211 138 024 066 6 2 PARAMETER CONTENTS AND SCOPES OF MASTER CONTROL MODULE Table 17 Parameter Contents and Scopes No Item Range...

Страница 26: ...e it is abnormal if the value has fallen below the set value 17 Return Value 0 200 85 Lower limit return value of voltage it is normal only when the value has exceeded the set value 18 Rated Frequency...

Страница 27: ...ain Open Delay 0 20 0 s 0 0 When the breaker fails to close for the first time then the module will open for the second time and the Again Open Delay begins after the delay has expired if it still fai...

Страница 28: ...gen voltage lasts abnormal after the delay has expired genset fault alarm will be initiated Scheduled Run Not Run Setting 1 Schedule Run 0 1 0 0 Disable 1 Enable 2 Run Mode 0 1 0 0 Off Load 1 On Load...

Страница 29: ...me Date 1 31 1 The date of genset not start monthly 14 Not Run Time Week Mon Sun Sunday Sunday Monday Tuesday Wednesday Thursday Friday Saturday 15 Not Run Time Hour 0 23 h 0 The time of genset not st...

Страница 30: ...er than the set value and delay is over it will take off load 16 NEL Over Power Trip 1 Delay 0 3600 s 5 17 NEL Over Power Trip 2 Set Value 0 200 100 When load power is greater than the set value and d...

Страница 31: ...o activate 11 Digital Input 6 0 159 0 Not Used 12 Active Type 0 1 0 0 Close to activate 1 Open to activate 13 Digital Input 7 0 159 0 Not Used 14 Active Type 0 1 0 0 Close to activate 1 Open to activa...

Страница 32: ...0 0 Output NO 1 Output NC 12 Contents Setting 0 159 0 Not Used 13 Relay Output 7 Active Type 0 1 0 0 Output NO 1 Output NC 14 Contents Setting 0 159 0 Not Used 15 Relay Output 8 Active Type 0 1 1 0 O...

Страница 33: ...36 Combined 2 or Out 2 Contents 0 159 0 Not Used 37 Combined 2 and Out Active Type 0 1 0 0 Output NO 1 Output NC 38 Combined 2 and Out Contents 0 159 0 Not Used 39 Combined 3 or Out 1 Active Type 0 1...

Страница 34: ...ntents 0 159 0 Not Used 59 Combined 6 or Out 2 Active Type 0 1 0 0 Output NO 1 Output NC 60 Combined 6 or Out 2 Contents Setting 0 159 0 Not Used 61 Combined 6 and Out Active Type 0 1 0 0 Output NO 1...

Страница 35: ...s parameter of monitoring module and master control mosule can be set simultaneously without affecting following communication 8 RS485 2 Baud Rate 0 3 2 0 2400bps 1 4800bps 2 9600bps 3 19200bps 9 RS48...

Страница 36: ...nd switch according to set priority Enable This load breaker can be allowed to control c o when it is in working position 5 Fixed C O Time 0 1 0 0 Disable 1 Enable Disable Output time is detected acco...

Страница 37: ...When the main breaker is manually closed opened prompt box Confirm to stepwise switch load will be popped out Press Up Down key to select Confirm Cancel then press Set key to confirm operation and ex...

Страница 38: ...Line Volt Amplitude Difference Multiple 0 1 00 0 20 It is the multiple that line voltage amplitude difference set value of PT break judgment accounts for rated voltage 6 Break Reset Volt Multiple 0 1...

Страница 39: ...lose ready signal inputs it needs to wait S2 PF input active before closing 14 S1 Close Key Input Same as S1 close key the self reset key is used to control S1 close 15 S2 Close Key Input Same as S2 c...

Страница 40: ...1 Closed Input QS1 Closed feedback input 43 S2 Closed Input QS2 Closed feedback input 44 Reserved 45 Reserved 46 Reserved 47 Reserved 48 Reserved 49 Reserved 50 Reserved 51 Reserved 52 Load 1 Close St...

Страница 41: ...r 8 closed status input 81 Load 8 Work Position Status Load breaker 8 work position status input 82 Load 8 Test Position Status Load breaker 8 test position status input 83 Load 8 Breaker Trip Load br...

Страница 42: ...input 112 Load 16 Close Status Load breaker 16 closed status input 113 Load 16 Work Position Status Load breaker 16 work position status input 114 Load 16 Test Position Status Load breaker 16 test po...

Страница 43: ...input 139 Load 22 Breaker Trip Load breaker 22 trip fault input 140 Load 23 Close Status Load breaker 23 closed status input 141 Load 23 Work Position Status Load breaker 23 work position status inpu...

Страница 44: ...iator externally When alarm mute input is active or 60s delay has expired it can remove the alarm 16 Reserved 17 Genset Start Delay Output when start signal is initiated 18 Genset Stop Delay Output wh...

Страница 45: ...47 S1 Genset Start When the system type is S1 Gen S2 Gen it controls the S1 genset start 48 S2 Genset Start When the system type is S1 Gen S2 Gen it controls the S2 genset start 49 ATS Power L1 ATS p...

Страница 46: ...ontrol When load stepwise switch selects external way load breaker close output 101 External Open Control When load stepwise switch selects external way load breaker open output 102 Reserved 103 Reser...

Страница 47: ...d breaker 14 open output 132 Load 15 Close Output Expand output control way load breaker 15 close output 133 Load 15 Open Output Expand output control way load breaker 15 open output 134 Load 16 Close...

Страница 48: ...ude themselves Example Contents of OR condition output S1 input port 1 is active Close when OR condition output S1 is active inactive close when active disconnect when inactive Contents of OR conditio...

Страница 49: ...lockwise until it reaches proper position Pull the fixing clip backwards towards the back of the module and ensure four clips are inside their allotted slots Turn the fixing clip screws clockwise unti...

Страница 50: ...ower Check starting batteries Check controller connection wirings Check DC fuse RS485 comm abnormal Check connection wirings Check setting of COM port is correct or not Check RS485 s A and B connectio...