HEM8500 Engine CAN Monitoring Controller User Manual Page 29 of 45
No.
Items
Parameters
Defaults
Description
14
Lower
Limit
Warning Value
(0~4000)
0
Setting of sensor lower limit warning value.
15
Warning Delay
(0~3600) s
2
Setting of sensor lower limit warning delay.
High Temperature Protection Setting (ECU)
1
Alarm Speed Set
(0~3000)r/min
1200
The system starts to alarm when the
controller measures the engine speed is
above the preset alarm speed.
2
Upper
Limit
Shutdown Enable
(0~1)
0
The upper limit shutdown enable set of high
ECU temperature.
3
Upper
Limit
Shutdown Value
(0~300)
98
The upper Limit shutdown value of high ECU
temperature.
4
Stop Delay Time
(0~3600)s
5
The stop delay time of high ECU
temperature.
5
Upper Limit Warn
Enable
(0~1)
0
The upper limit warn enable set of high ECU
temperature.
6
Upper Limit Warn
Value
(0~300)
92
The upper limit warn value of high ECU
temperature.
7
Upper Limit Warn
Return Value
(0~300)
85
The upper limit warn return value of high
ECU temperature.
8
Warn Delay
(0~3600)s
2
The upper limit warn delay value of high
ECU temperature.
Low OP Protection Setting ( ECU)
1
Alarm Speed Set
(0~3000)r/min
1200
The system starts to alarm when the
controller measures the engine speed is
above the preset alarm speed.
2
Lower
Limit
Shutdown Enable
(0~1)
The lower limit shutdown enable set of low
ECU oil pressure.
3
Lower
Limit
Shutdown Value
(0~1000)
The lower Limit shutdown value of low ECU
oil pressure.
4
Stop Delay Time
(0~3600)s
The stop delay time of low ECU oil pressure.
5
Lower Limit Warn
Enable
(0~1)
The lower Limit warn enable set of low ECU
oil pressure.
6
Lower Limit Warn
Value
(0~1000)
The lower limit warn value of low ECU oil
pressure.
7
Lower Limit Warn
Return Value
(0~1000)
The lower limit warn return value of low ECU
oil pressure.
8
Warn Delay
(0~3600)s
The lower limit warn delay value of low ECU
oil pressure.
Digital Input Ports
Digital Input Port 1
1
Content Setting
(0~50)
0
Not used.
2
Active Type
(0~1)
0
0: Close; 1: Open