HEM8500 Engine CAN Monitoring Controller User Manual Page 28 of 45
No.
Items
Parameters
Defaults
Description
Value
9
Stop Delay
(0~3600) s
5
Sensor lower limit stop delay setting.
10
Upper
Limit
Warning Enabled
(0~1)
1
Sensor upper limit warning enabled setting.
11
Upper
Limit
Warning Value
(0~6000)
92
Sensor upper limit warning value setting.
12
Warning Delay
(0~3600) s
2
Sensor upper limit warning delay setting.
13
Lower
Limit
Warning Enabled
(0~1)
0
Sensor lower limit warning enabled setting.
14
Lower
Limit
Warning Value
(0~4000)
0
Sensor lower limit warning value setting.
15
Warning Delay
(0~3600) s
2
Sensor lower limit warning delay setting.
Aux Sensor 3~4
1
Sensor Type
(0~3)
0
0: Not Used
1: Pressure
2: Temperature
3: Fuel Level
2
Curve Type
(0~15)
0
Change according to sensor type;
Refer to Table 21 for detailed sensor type
list.
3
Alarm
Speed
Setting
(0~3000) r/min
1200
When controller measures engine speed is
above preset alarm speed value, system
starts to detect alarms.
4
Upper Limit Shut
Enabled
(0~1)
1
Setting of sensor upper limit shutdown
enable.
5
Upper Limit Shut
Value
(0~6000)
98
Setting of sensor upper limit shutdown
value.
6
Stop Delay
(0~3600) s
5
Setting of sensor upper limit shutdown
delay.
7
Lower Limit Shut
Enabled
(0~1)
0
Setting of sensor lower limit shutdown
enable.
8
Lower Limit Shut
Value
(0~400)
0
Setting of sensor lower limit shutdown
value.
9
Stop Delay
(0~3600) s
5
Setting of sensor lower limit shutdown
delay.
10
Upper
Limit
Warning Enabled
(0~1)
1
Setting of sensor upper limit warning
enable.
11
Upper
Limit
Warning Value
(0~6000)
92
Setting of sensor upper limit warning value.
12
Warning Delay
(0~3600) s
2
Setting of sensor upper limit warning delay.
13
Lower
Limit
Warning Enabled
(0~1)
0
Setting of sensor lower limit warning
enable.