HEM8500 Engine CAN Monitoring Controller User Manual Page 25 of 45
8
SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS
8.1
CONTENTS AND SCOPES OF PARAMETER SETTING
Table 14 Parameter Setting Contents and Scopes
No.
Items
Parameters
Defaults
Description
Timer Settings
1
Pre-heat Delay
(0~3600) s
0
Time of pre-powering heat plug before
starter is powered up.
2
Cranking Time
(3~60) s
8
Time of starter power on
3
Crank Rest Time
(3~60) s
10
The waiting time before second power up
when engine start fail.
4
Safety On Delay
(0~3600) s
10
A short of running time after engine start up.
5
Cooling Time
(0~3600) s
10
Cooling time for engine before stop.
6
ETS Solenoid Hold
(0~3600) s
20
ECU power off time after pressing stop key.
7
Fail to Stop Time
(0~3600) s
0
Time from gen-set ETS solenoid hold time
expired to stop completely.
8
Power Off Delay
(15~150) s
35
The delay time for power off after pressing
power key.
9
Wake Up Timeout
(0~3600) s
20
When engine status is in normal running, no
active delay time of wake up input has been
detected.
Engine Settings
1
Engine Type
(0~39)
1
Default: Common ECU Engine.
When connected to J1939 engine, choose
the corresponding type.
2
SPN Alarm Version (1~3)
1
Selection for SPN alarm version.
3
Start Attempts
(1~30) times
1
Max. crank times. When reach this number,
controller will send start failure signal.
4
Disconnect Speed
(1~1000) r/min
350
When engine speed is higher than the set
value, starter will be disconnected.
5
Battery Rated Volt
(0~60.0) V
24.0
Provide standard judgment for battery over
/under voltage.
6
Battery Over Volt
Warn
(0~200) %
125
When battery volt is higher than preset volt
percentage, controller will send battery
voltage high warning alarm.
7
Battery Under Volt
Warn
(0~200) %
80
When battery volt is lower than preset volt
percentage, controller will send battery
voltage low warning alarm.
8
Throttle
Start
Speed
0~2000 r/min
800
The minimum engine speed of throttle can
be adjusted.
9
Throttle
Max. 0~3000 r/min
2500
The max engine speed of throttle can be