12 FAULT FINDING 

Symptom 

Possible Solutions 

Controller  no  response  with 
power. 

Check controller wring. 

Genset  running  while  ATS 
not transfer 

Check ATS; 
Check the connection wirings between the controller and the 
ATS. 

Electrical 

parameters 

detection error 

Check controller wring; 
Modify electrical parameters detection value. 

PC software communication 
failure 

Check communication port setting and connections. 

 

Содержание HAT530

Страница 1: ...HAT530 ATS CONTROLLER USER MANUAL Smartgen Technology ...

Страница 2: ... cn http www smartgen cn Email sales smartgen cn All rights reserved No part of this publication may be reproduced in any material form including photocopying or storing in any medium by electronic means or other without the written permission of the copyright holder Smartgen Technology reserves the right to change the contents of this document without prior notice If colors of actual products are...

Страница 3: ...are Version Version Date Note 1 0 2014 06 23 Original release Clarification of notation used within this publication SIGN INSTRUCTION NOTE Highlights an essential element of a procedure to ensure correctness ...

Страница 4: ...BUTTON OPERATION 10 5 1 PRIORITY SETTING 11 5 2 AC SYSTEM SETTING 12 5 3 DELAY ADJUSTMENT 13 5 4 RESTORE FACTORY DEFAULT 14 6 PROGRAMMED PARAMETER AND RANGE 15 6 1 PARAMETERS TABLE 15 6 2 INPUT OUTPUT FUNCTION DESCRIPTION 18 7 OPERATION CONTROL 19 8 DESCRIPTION OF CONNECTING TERMINALS 20 9 ATS POWER SUPPLY 22 10 TYPICAL WIRING DIAGRAM 23 11 INSTALLATION 25 12 FAULT FINDING 26 ...

Страница 5: ...oltage power lost over under voltage over under frequency loss of phase phase sequence wrong and control ATS to transfer after the delay has expired This controller is suitable for NO Breaking ATS and ONE Breaking ATS When 1 power is abnormal the controller will send signal to start genset after the 1 abnormal delay has expired Three remote remote control remote measurement and remote communicatio...

Страница 6: ... The voltage normal delay of 1 or 2 can be set in 0 60 seconds and the Genset start delay can be set in 0 3600 seconds The voltage abnormal delay of 1 or 2 can be set in 0 60 seconds and the Genset stop delay can be set in 0 3600 seconds 1 power priority Auto Manual No priority and 2 power priority can be set via controller front panel Closing output signal can be set as on intervals or as continu...

Страница 7: ...C systems 3 phase 4 wires 2 phase 3 wires and single phase 2 wire Controller has strong ability of anti electromagnetic interference can be used under complex electromagnetic interference environment Modular design self extinguishing ABS plastic shell pluggable terminal built in mounting compact structure with easy installation ...

Страница 8: ... AC250V Volts free output AUX OUTPUT 1 16A AC250V Volts free output AUX OUTPUT 2 16A AC250V Volts free output Gen Start Relay 7A AC250V Volts free output 1 Close Input COM2 connect is active 2 Close Input COM2 connect is active Forced Open Input COM2 connect is active Communication LINK interface MODBUS Protocol Case Dimensions 139mmx120mmx48mm Panel Cutout 130mmx111mm Working Conditions Temperatu...

Страница 9: ...s no 2 power 1 Close Indicator It is illuminated when 1 power auxiliary contactor is active while off when it is deactivated 2 Close Indicator It is illuminated when 2 power auxiliary contactor is active while off when it is deactivated Auto Mode Indicator It is illuminated when the controller is in auto mode while off the controller is in manual mode Manual Mode Indicator It is illuminated when t...

Страница 10: ...r release the button Pressing and holding the button for more than 7s all LEDs are flashing 500ms per time to enter into parameter setting status users can set the parameters after release the button If users don t want to set the parameters under this status 1 Pressing and holding the button again until all LEDs are flashing 5 times rapidly 200ms per time which means the controller enter into nor...

Страница 11: ...ity 2 power indicator illuminates and 1 power indicator extinguishes No Priority 1 power and 2 power indicators are illuminating at the same time 3 After adjusting press when 1 power indicator auto indicator and 2 power indicator are illuminated the adjusted power priority has been saved The controller will back to normal status automatically after all LEDs are flashing 5 times rapidly and control...

Страница 12: ...e 1 close indicator illuminates 3 phase 4 wire 1 close indicator 2 close indicator and manual mode indicator illuminates simultaneously 2 phase 3 wire 1 close indicator and manual mode indicator illuminates simultaneously 4 After adjusting press when 1 power indicator auto indicator and 2 power indicator are illuminating the adjusted AC system has been saved The controller will back to normal stat...

Страница 13: ...uminated release the two buttons then the auto indicator and 1 2 power indicators are extinguished simultaneously which means the delay timer of the controller can be set 1 power abnormal delay adjust 1 Normal potentiometer 2 power abnormal delay adjust 2 Normal potentiometer b After adjusting the delays press When 1 2 power indicator and automatic indicator are illuminated simultaneously the adju...

Страница 14: ...ns then the auto indicator and 1 2 power indicators are extinguished simultaneously which means the default delay value of the controller can be set b Press when 1 2 power indicator and auto indicator are illuminated simultaneously the factory default has been restored The controller will back to normal status automatically after all LEDs are flashing 5 times rapidly and controller will work accor...

Страница 15: ...ontinuous output 06 Open Delay 1 20 s 5 Open relay output pulse 07 Transfer Interval 0 60 s 1 It is the delay from 1 power open to 2 power close or from 2 power open to 1 power close 08 Exceed Transfer 0 20 0 s 0 0 It is the extra output delay of the close relay after the closing signal has received 09 Start Delay 0 3600 s 1 When voltage is abnormal start delay begins start signal is initiated aft...

Страница 16: ...he set value 21 Over Frequency Return 100 120 104 Frequency upper limit return value it is normal only when the frequency fallen below the set value 22 Under Freq Enable 0 1 0 0 Disable 1 Enable 23 Under Frequency 80 100 90 Frequency lower limit it is abnormal when the frequency has fallen below the set value 24 Under Frequency Return 80 100 96 Frequency lower limit return value it is normal only ...

Страница 17: ... the back panel terminal AC system and priority selection can be set via panel button or PC software while other parameters can be set via PC software only 1 Normal Delay set value must be no less than 1 Abnormal Delay otherwise 1 Normal Delay set value will be forced set as 1 Abnormal Delay set value The matters need attention of 2 is same as 1 If motor driving type ATS e g SOCOMEC VS is applied ...

Страница 18: ...t when 1 2 voltages are abnormal simultaneously 06 Auto Mode In will output in automatic mode 07 Manual Mode In will output in manual mode 08 Gens start N O When generator starts output Relay closed 09 Gens start N C When generator starts output Relay released 10 1 Close Output 1 Switch ON signal output 11 Open Output Switch OFF signal output 12 2 Close Output 2 Switch ON signal output 13 Reserved...

Страница 19: ...TION CONTROL Auto Manual operation When controller is running pressing key can set the controller as Auto mode or Manual mode indicate by automatic and manual indicators In Manual mode press key load will be transferred to 1 power supply press key load will be transferred to 2 power supply ...

Страница 20: ...Volt free relay contact output Rated 16A 5 COM 6 NO 7 1 Close Output Volt free relay contact output Normally Open Output Rated 5A 8 2 Close Output Volt free relay contact output Normally Open Output Rated 5A 9 Open Output Volt free relay contact output Normally Open Output Rated 5A 10 COM1 Output COM of close switch and open switch COM1 11 GEN Start Volt free relay contact output Normally Close Ou...

Страница 21: ...nput Connect COM2 is active 18 2 Close Input Detection of 2 ATS closing status auxiliary contact input Connect COM2 is active 19 Force Open When active the ATS is in Neutral Position Connect COM2 is active 20 COM2 Input COM COM2 21 A2 2 AC 3 phase 4 wire voltage input For single phase only connect A2 N2 22 B2 23 C2 24 N2 LINK Communication Port Communicate with PC Program update ...

Страница 22: ...auxiliary output 1 and auxiliary output 2 to ATS power supplies When controller power is ON the default configuration of auxiliary output 1 is ATS power A while s auxiliary output 2 is ATS power N If the ATS power supplied by Line Voltage same procedures as above but change phase N to phase voltage and the auxiliary output 2 should be configured as ATS power B Parameters can be set via PC software...

Страница 23: ...HAT530 ATS CONTROLLER HAT530 ATS CONTROLLER 2014 06 23 Version 1 0 Page 23 of 26 10TYPICAL WIRING DIAGRAM ATySM3s Wiring Diagram ATyS3s Wiring Diagram ...

Страница 24: ...ld choose proper fuse capacity according to the actual power consumption If SOCOMEC VS is applied the Close delay and Open delay must be no less than 5s Default 5s 2 phase 3 wire Wiring Diagram Single phase 2 wire Wiring Diagram NOTE Above pictures take the AC 220V voltage as example If AC 110V voltage is applied in actual use please contact with Smartgen technical staff to get the specific wiring...

Страница 25: ...HAT530 ATS CONTROLLER HAT530 ATS CONTROLLER 2014 06 23 Version 1 0 Page 25 of 26 11INSTALLATION ...

Страница 26: ...sponse with power Check controller wring Genset running while ATS not transfer Check ATS Check the connection wirings between the controller and the ATS Electrical parameters detection error Check controller wring Modify electrical parameters detection value PC software communication failure Check communication port setting and connections ...

Отзывы: