HAT530 ATS CONTROLLER
HAT530 ATS CONTROLLER 2014-06-23 Version 1.0 Page 17 of 26
No.
Item
Range
Default
Description
DESCRIPTION
NOTE
:
“1# Normal Delay” and “2# Normal Delay” can be set only via the potentiometer which
locate nearby the back panel terminal.
“1# Abnormal Delay” and “2# Abnormal Delay” can be set via the PC software or
potentiometer which locate nearby the back panel terminal.
AC system and priority selection can be set via panel button or PC software while other
parameters can be set via PC software only.
1# Normal Delay set value must be no less than 1# Abnormal Delay, otherwise, 1# Normal
Delay set value will be forced set as 1# Abnormal Delay set value. The matters need
attention of 2# is same as 1#.
If motor driving type ATS (e.g. SOCOMEC VS) is applied, the Close delay and Open delay
must be no less than 5s; If magnet driving type ATS (e.g. SOCOMEC ATySM3s) is applied,
the Exceed Transfer delay must be set as 0.