HAT160 ATS CONTROLLER USER MANUAL
HAT160 ATS Controller 2020-03-14 Version 1.1 Page 16 of 21
Table 8 Parameter Setting Contents and Range (2)
No.
Item
Range
Default
Description
1 Power Supply
(0-1)
0
0: 3Phase 4Wire
1: 1Phase 2Wire
2 Rated Volt
(170-270)V
230
Provide standard for over/under volt judgment.
Provide standard for close volt and aux. alarm
volt.
3 Rated Freq
(50.0-60.0)Hz 50.0
Provide standard for over/under frequency
judgment.
4
Over Volt Monitor
Enabled
(0-1)
1
0: Disabled
1: Enabled
5 Over Volt Threshold
(100-120)%
115
Threshold
6 Over Volt Return
(100-120)%
113
Return
7
Under Volt Monitor
Enabled
(0-1)
1
0: Disabled
1: Enabled
8 Under Volt Threshold
(70-100)%
75
Threshold
9 Under Volt Return
(70-100)%
77
Return
10
Over Freq Monitor
Enabled
(0-1)
1
0: Disabled
1: Enabled
11 Over Freq Threshold
(100-120)%
110
Threshold
12 Over Freq Return
(100-120)%
104
Return
13
Under Freq Monitor
Enabled
(0-1)
1
0: Disabled
1: Enabled
14 Under Freq Threshold (80-100)%
90
Threshold
15 Under Freq Return
(80-100)%
96
Return
16
Loss of Phase Monitor
Enabled
(0-1)
1
0: Disabled
1: Enabled (Settled delay: 3s)
NOTE
: The parameters in this form can only be set via computers.