DIN16A DIGITAL INPUT MODULE USER MANUAL
DIN16A Digital Input Module Version 1.0 2017-04-15 Page 7 of 12
5 DEFINITION OF INPUT PORT
5.1 DEFINITION CONTENTS OF DIGITAL INPUT
NO.
Items
Contents
Description
1
Function set
(0-50)
More details please refer to Function
Setting.
2
Active Type
(0-1)
0
:
Close to activate
1
:
Open to activate
3
Effective Range
(0-3)
0
:
From Safety on
1
:
From Crank
2
:
Always
3
:
Never
4
Effective Action
(0-2)
0
:
Warn
1
:
Shutdown
2
:
Indication
5
Input Delay
(0-20.0)s
6
Display string
User-defined names of
input port
Input port names can be edited via PC
software only.
5.2 FUNCTION SETTING
No.
Contents
Description
0
Not used
1
User-defined
Users configured input port settings
2
Alarm Mute
Can prohibit “Audible Alarm” output when input is active.
3
Reset alarm
Can reset all alarms when input is active.
4
Raise Speed
The generator will increase speed by GOV when the input
is active.
5
Drop Speed
The generator will decrease speed by GOV when the input
is active.
6
Reserved
7
Reserved
8
Lamp test
All LED indicators are illuminating when input is active.
9
Local mode
Places generator into its local mode
10
Remote mode
Places generator into its remote mode.
11
Remote start
Automatically starts the generator in remote mode when
the input is active. Only the active shutdown input will be
able to stop the generator. (Inch or hold the button for
more than 1s)
12
Remote stop
Stops the running generator in remote mode when the
input is active.
13
Remote start/stop
Automatically starts the generator in remote mode; the
generator will shut down when this input is deactivated.
14
Pre-lubricate
If output is set as pre-lubrication output, the relay
disconnects after the set pre-lubrication delay.