A. C. MODULAR GENERATOR SYSTEM
Page 40 of 53
4.
The Command & Control Center will flash a fault when 250 hours have passed
since the previous filter change. After replacing the filter, this fault can be removed
from the Command & Control Center, and the filter run time can be reset by
performing the following steps:
Step a: Press Mode until
,
,
and
appear.
Step b: Hold Mode switch
down and press On/Off three
times in a row to clear the
fault.
Procedure will also work
in the Oil Filter Hours
Information display
Example of oil filter service warning display
Figure 26
a. Press the Mode switch repeatedly until one of the screens shown in Figure 26
appears.
b. While holding the Mode switch down, press and release the On/Off switch three
times in succession, then release the Mode switch. The Oil Filter Fault display
will be removed and replaced by another screen. The fault has been cleared
and the timer reset.
c. When the fault has been cleared, the system automatically enters purge mode
to purge any entrapped air from the hydraulic lines. See Figure 13. The system
must be purged for 30 minutes, 20 of which must be with the generator ON.
Turn off the main power breaker during purge (see Figure12). While purging,
the system will not produce usable electrical power.