Configuration
3.23
Figure 3.22 - Step 2 - IF303
Figure 3.23 - Step 3 - IF303
Figure 3.24 - Step 4 - IF303
Remove the
magnetic tool from
orifice
S
.
Insert the magnetic
tool in orifice
S
once
more and
LOC ADJ
should be displayed.
Place the magnetic tool in
orifice
Z
. In case this is the first
configuration, the option shown
on the display is the
TAG
with
its corresponding mnemonic
configured by the Configuration
Tool. Otherwise, the option
shown on the display will be the
one configured in the prior
operation. By keeping the tool
inserted in this orifice, the local
adjustment menu will rotate.
This parameter is used to
calibrate the lower current
point. In order to range the
lower value, simply insert the
magnetic tool in orifice
S
as
soon as lower is shown on the
display. An arrow pointing
upward (
↑
) increment the value
and an arrow pointing
downward (
↓
) decrement the
value. Apply the 4.00 mA
current in the
1
and
4
terminals. Adjust the current
showed on the display to 4.00
mA..
In order to decrement
the lower value, place
the magnetic tool in
orifice
Z
to shift the
arrow to the downward
position and then, by
inserting and keeping
the tool in orifice
S
, it is
possible to decrement
the lower value.
This parameter is used to
calibrate the upper current
point. In order to range the
upper value, simply insert the
magnetic tool in orifice
S
as
soon as upper is shown on the
display. An arrow pointing
upward (
↑
) increment the value
and an arrow pointing
downward (
↓
) decrement the
value. Apply the 20.0 mA
current in the
1
and
4
terminals. Adjust the current
showed on the display to 20.0
mA.