FY303 – Operation, Maintenance and Instructions Manual
3.6
Parameter
Transducer Block Description
DIAGNOSES_STATUS
Indicates the status of diagnoses:
{ 0, "None"},
{ 2, "Output Module Not Initialized"},
{ 4, "No Valve Movement or Slow Valve Movement or Low Air Supply or No Magnet Detected"},
{ 6, "(No Valve Movement or Slow Valve Movement or Low Air Supply or No Magnet Detected)
and (Output Module Not Initialized)"},
{ 8, "Travel Limit Exceeded"},
{ 10, "Travel Limit Exceeded and Output Module Not Initialized"},
{ 12, "Travel Limit Exceeded and (No Valve Movement or Slow Valve Movement or Low Air
Supply or No Magnet Detected)"},
{ 14, "(Travel Limit Exceeded) and (No Valve Movement or Slow Valve Movement or Low Air
Supply or No Magnet Detected) and (Output
Module Not Initialized)"},
{ 16, "Temperature Out of work range"},
{ 18, "Temperature Out of work range and Output Module Not Initialized"},
{ 20, "Temperature Out of work range and (No Valve Movement or Slow Valve Movement or
Low Air Supply or No Magnet Detected)"},
{ 22, "Temperature Out of work range and (No Magnet Detected and Output Module Not
Initialized)"},
{ 24, "Travel Limit Exceeded and Temperature Out of work range"},
{ 26, "Travel Limit Exceeded and Temperature Out of work range and Output Module Not
Initialized"},
{ 28, "Travel Limit Exceeded and Temperature Out of work range and (No Valve Movement or
Slow Valve Movement or Low Air Supply or No Magnet Detected)"},
{ 30, "Travel Limit Exceeded and Temperature Out of work range and (No Valve Movement or
Slow Valve Movement or Low Air Supply or No Magnet Detected) and Output Module Not
Initialized"},
{ 32, "Output Module Not Detected"}
DIGITAL_HALL_VALUE
Value and Status for Hall sensor.
HALL_COMPENSATED
Value for Hall sensor after compensation of offset.
HALL_OFFSET_CONTROL
Enable and disable for offset compensation.
{0, "Disable"},
{1, "Enable"}
READ_HALL_CAL_POINT_HI
The highest calibrated point for Hall sensor.
READ_HALL_CAL_POINT_LO
The lowest calibrated point for Hall sensor.
DA_OUTPUT_VALUE
Value and status for DA output.
USER_DA_CAL_POINT_HI
The highest calibrated point for DA output.
USER_DA_CAL_POINT_LO
The lowest calibrated point for DA output.
PIEZO_ANALOG_VOLTAGE
The analog voltage for piezo.
POT_DC
The value for POT DC.
MAIN_LATCH
MAIN ANALOG SWITCH USED BY HARDWARE.
Содержание fy303
Страница 1: ...OPERATION MAINTENANCE AND INSTRUCTION MANUAL Profibus PA Valve Positioner JUL 16 F Y 3 0 3 M E...
Страница 7: ...Kpuvcnncvkqp Hnqyejctv XKK Kpuvcnncvkqp Hnqyejctv...
Страница 8: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn XKKK...
Страница 20: ...FY303 Operation Maintenance and Instructions Manual 1 12...
Страница 26: ...FY303 Operation Maintenance and Instructions Manual 2 6...
Страница 69: ...Configuration 3 43 Figure 10 Sensor Pressure Configuration Data...
Страница 70: ...FY303 Operation Maintenance and Instructions Manual 3 44...
Страница 88: ...FY303 Operation Maintenance and Instructions Manual 5 6...
Страница 94: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C08...
Страница 95: ...Egtvkhkecvkqpu Kphqtocvkqp C09 Eqpvtqn Ftcykpi FM Approvals Factory Mutual...
Страница 96: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C0 CSA Canadian Standards Association...
Страница 97: ...Egtvkhkecvkqpu Kphqtocvkqp C0...
Страница 98: ...H 525 Qrgtcvkqp Ockpvgpcpeg cpf Kpuvtwevkqpu Ocpwcn C032...
Страница 114: ...6 Mounting Instructions...