DFI302 – User’s Manual
14.20
Check conditions
Nrio_BK>Nrio_main
I
s CPU configured?
Yes
No
CPU gets active
Yes
Back up CPU gets
active
Main CPU gets
active
No
Nrio_BK= number of RIO modules seen by
the backup CPU
Nrio_main= number of RIO modules seen
by the main CPU
Flow chart representing the check conditions procedure
Communication with Remote Input and Output (RIO) Modules
The DF66 modules are scanned only if the name of the configuration and data are the same in the
main Coprocessor and DF66. The passive Coprocessor sends polling commands to check
periodically whether it is necessary to assume the control.
As seen in the system architecture picture, the DF66 modules are connected to the system through
two different and redundant channels.
There are two ports to be considered:
DF66 Active Port:
Port being scanned by the active Coprocessor, i.e., through this port the Modbus
variables are read and written.
DF66 Passive Port:
In this port the passive Coprocessor checks the conditions of the active and
passive ports.
Switch Over Procedure
During the normal functioning of the system, there’s a switching procedure. It is based on the
number of the DF66 that the active Coprocessor can communicate with (
NRIO active
) and the
number of DF66s that the passive Coprocessor can communicate with (
NRIO passive
).
If NRIO active is shorter than NRIO passive, then there is a switching over procedure that makes the
current active Coprocessor the passive Coprocessor and the old passive Coprocessor the current
active Coprocessor. This procedure ensures that the system reads the biggest amount of I/O
Modbus variables.
LEDS for Status Indication
A solid RUN LED (green, ON or OFF) indicates if the Coprocessor is in Active state while a blink
RUN LED indicates that the Coprocessor is in Passive state.
A solid HOLD LED (yellow, ON or OFF) indicates if the Coprocessor has been configured
properly, while a blink HOLD LED indicates that it was not.
A solid FORCE LED (red, ON or OFF) indicates if the Coprocessor is in FORCE-IN, FORCE-
OUT or SAFE-OUT mode, or not.
FORCE LED indicator on Passive Coprocessor is blinking. It indicates that the hardware settings
is not correct (rotary switch, BR for DF66 or firmware version).
Содержание DFI302
Страница 1: ...D F I 3 0 2 M E FEB 05 FOUNDATION...
Страница 4: ...DFI302 User s Manual IV...
Страница 6: ...DFI302 User s Manual VI...
Страница 20: ...DFI302 User s Manual 2 4 o n 1 2 3 4 o f f HUB Detail A Detail A H1 Channel Ground Neutral Line...
Страница 30: ...DFI302 User s Manual 2 14...
Страница 46: ...DFI302 User s Manual 3 16...
Страница 56: ...DFI302 User s Manual 4 10...
Страница 60: ...DFI302 User s Manual 5 4...
Страница 64: ...DFI302 User s Manual 6 4 Dimensions...
Страница 82: ...DFI302 User s Manual 7 18...
Страница 88: ...DFI302 User s Manual 8 6...
Страница 92: ...DFI302 User s Manual 9 4...
Страница 136: ...DFI302 User s Manual 10 44...
Страница 162: ...DFI302 User s Manual 11 26...
Страница 182: ...DFI302 User s Manual 12 20...
Страница 216: ...DFI302 User s Manual 15 12...