DFI302 – Configuring DFI OLE Server
4.7
HSE Device Definition
Any device Fieldbus Foundation connected directly with an HSE Media. All the HSE Devices have
one FDA Agent, one HSE SMK and one HSE NMA VFD. For instance, Linking Devices, I/O
Gateways and HSE Field Devices. The DFI302 is a Linking Device.
•
Please certify that DFI302 or any HSE Device is installed correctly under the Network.
•
File:
HseSvr.exe
•
ProgID:
Smar.HSEOLEServer.0
•
Name: Smar OPC & Conf Server for HSE
SmarOleServer.ini configuration
SmarOleServer.ini file, located under OleServers folder provides some SECTION and KEYS which
are permited enable and disable logs, set timeouts, configure network details, etc. Let’s to describe
these sections:
•
In Log and LogForOPC Sections, it is possible to enable some log features and see the results
in Events.log and EventOPC.log files respectively. Both files have its (.log#) file used for swap.
[Log]
GENERAL=0
DEBUG=0
MEMORY=0
INIT=1
DRIVER=0
TRANSFER=0
TRANSACTION=0
CONF=0
OPC=0
OPCDEBUG=0
IDSHELL=0
;=0 (Default) Log disabled
;=1 Enable log and see the results in Events.log and Events.log#
[LogForOPC]
GENERAL=0
;=0 (Default) Log disabled
;=1 Enable log and see the results in EventOPC.log and EventOPC.log#
•
In NIC Adapter Section, in the case of more than one NIC adapter are installed in the machine,
choose the desired NIC adapter to be connected with the local DFI OLE Server.
[NIC Adapter]
; If more than one NIC (Network Interface Card) are installed in the local machine
; it is necessary to inform the DFI OLE Server to use one (NIC) or two (NIC and NIC2) adapters.
; In the NIC key (next lines), set the IP which is configured in each NIC and remove ';'
;NIC=192.168.164.202
;NIC2=192.168.163.202
•
In DFI Time Settings Section, tune the better startup time which the DFI OLE Server takes to look for
DFI302 spread to the network. The default time use to be enough if not using routers.
[DFI Time Settings]
; Define a delay which the server will wait till complete DFI connection
;=13 (Default) 3 seconds before concluding server connection with DFIs
NETWORK_STARTUP=13
•
In Remote DFI Section, when using Routers in the Network topology, insert the other IPs located out
of the local subnet. Do not forget to tune in DFI Time Settings Section, the better time necessary to
DFI OLE Server.
[Remote DFI]
; Specify on this section IPs to be reached in remote networks.
Содержание DFI302
Страница 1: ...D F I 3 0 2 M E FEB 05 FOUNDATION...
Страница 4: ...DFI302 User s Manual IV...
Страница 6: ...DFI302 User s Manual VI...
Страница 20: ...DFI302 User s Manual 2 4 o n 1 2 3 4 o f f HUB Detail A Detail A H1 Channel Ground Neutral Line...
Страница 30: ...DFI302 User s Manual 2 14...
Страница 46: ...DFI302 User s Manual 3 16...
Страница 56: ...DFI302 User s Manual 4 10...
Страница 60: ...DFI302 User s Manual 5 4...
Страница 64: ...DFI302 User s Manual 6 4 Dimensions...
Страница 82: ...DFI302 User s Manual 7 18...
Страница 88: ...DFI302 User s Manual 8 6...
Страница 92: ...DFI302 User s Manual 9 4...
Страница 136: ...DFI302 User s Manual 10 44...
Страница 162: ...DFI302 User s Manual 11 26...
Страница 182: ...DFI302 User s Manual 12 20...
Страница 216: ...DFI302 User s Manual 15 12...