Event number
Message, cause and corrective measures
7101
SD card defective
The SD memory card is not formatted.
Corrective measures:
• Re-format the SD memory card.
• Re-save the files to the SD memory card.
7105
Param. setting failed
Parameters could not be set using the memory card. The inverter continues
feeding power into the grid.
Corrective measures:
• Ensure that the parameters are set correctly.
• Ensure that the SMA Grid Guard code is available.
7106
Update file defect.
Update file on the memory card is defective.
Corrective measures:
• Reformat the memory card.
• Re-save the files to the memory card.
7102
Parameter file not found or defective
The parameter file was not found or is defective. The update failed. The in-
verter continues feeding power into the grid.
Corrective measures:
• Copy the parameter file to the correct folder again.
7110
No update file found
No update file has been found.
Corrective measures:
• Copy the update file to the memory card folder. Select the folder
\UPDATE
.
7201 to 7202
Data stor. not poss.
Internal error. The inverter continues to feed into the utility grid.
Corrective measures:
• Contact the Service.
7303
Update main CPU failed
The cause must be determined by the Service.
Corrective measures:
• Contact the Service.
10 Troubleshooting
SMA Solar Technology America LLC
Installation Manual
47
STPTL-US-10-IA-xx-17
ENGLISH
Содержание SUNNY TRIPOWER 12000TL-US
Страница 232: ...www SMA America com ...