With voltage changes, only the phase voltages are considered. If the set values
are present as line-to-line voltages, these have to be converted to phase volt-
ages.
U =
U
3
Name
Value/range
Default value
Voltage monitoring upper maximum threshold as
RMS value
277 V to 332.4 V
332.4 V
Voltage monitoring median maximum threshold
(Overvoltage/Fast)
277.0 V to 332.4 V
332.4 V
Voltage monitoring lower maximum threshold
(Overvoltage/Slow)
277.0 V to 304.7 V
304.7 V
Voltage monitoring upper minimum threshold
(Un-
dervoltage/Slow)
138.5 V to 277.0 V
243.8 V
Voltage monitoring of median minimum threshold
(Undervoltage/Fast)
138.5 V to 277.0 V
138.5 V
Voltage monitoring lower minimum threshold as
RMS value
138.5 V to 277 V
138.5 V
Voltage monitoring upper maximum threshold as
RMS value tripping time
0.1 s to 60 s
0.2 s
Voltage monitoring median max. threshold trip.time
(Overvoltage/Fast, maximum time)
0.1 s to 60 s
0.16 s
Voltage monitoring lower max. threshold trip. time
(Overvoltage/Slow, maximum time)
0.1 s to 60 s
1.0 s
Voltage monitoring upper min. threshold trip. time
(Undervoltage/Slow, maximum time)
0.1 s to 1000 s
2.0 s
Voltage monitoring median min. threshold trip.time
(Undervoltage/Fast, maximum time)
0.1 s to 1000 s
0.16 s
Voltage monitoring lower minimum threshold as
RMS value tripping time
0.1 s to 60 s
0.2 s
Frequency monitoring upper minimum threshold
(Underfrequency)
44 Hz to 60 Hz
59.3 Hz
Frequency monitoring lower maximum threshold
(Overfrequency)
50 Hz to 65 Hz
60.5 Hz
Frq. monitoring upper min. threshold trip. time
(Un-
derfrequency, maximum time)
0.1 s to 30000 s
0.16 s
Frq. monitoring lower max. threshold trip. time
(Overfrequency, maximum time)
0.1 s to 9000 s
0.16 s
8 Configuration
SMA Solar Technology America LLC
Installation Manual
STPTL-US-10-IA-xx-17
38