Appendix B Technical Data
SMA
Technologie AG
Page 42
SC-100-13:SE2407
Installation manual
Please note:
•
the “Sunny Central Transport Instructions”,
•
the “Sunny Central Installation Guide”,
•
when installing the SC 100 Outdoor, a suitable foundation, sufficient ventilation
and appropriate sun shading systems are necessary
Monitored overvoltage protectors for
auxiliary supply
optional
Standards
EMC
EN 61000-6-2, EN
61000-6-4
Grid monitoring
per VDEW regulations
CE conformity
yes
Protection rating and ambient conditions
Protection rating per EN 60529
IP44 / IP54
Permissible ambient temperature
T
-20 °C ... +50 °C
c)
Relative humidity, not condensing
U
air
15 ... 95 %
Max. altitude (above sea level)
NN
1,000 m
Air quality (minimum requirements)
per EN 60721-3-3
class 3S2
Fresh air consumption
V
air
2,300 m³/h
Air duct for outdoor installation
drawn through roof
blown out through base
a. Specifications apply to irradiation values = 1000
b. Terminal for an analog sensor provided by the customer in two-wire systems
c. Compliance with nominal values up to an ambient temperature of +40 °C, with an
ambient temparature of +50 °C maintanance of the nominal values up to two houres
Sunny Central data
Symbol
SC100 outdoor
Year
kWp
kWh
⋅