Installation requirements
Installation Guide
SB1100LV-11:SE2006
Page 17
AC cable system impedance should not exceed 1 ohm. This is necessary, amongst other
things, for the correct operation of impedance observation. In addition, we recommend
dimensioning the conductor cross-section so that line losses do not exceed 1% at the
nominal power. Line losses depending on the cable length and cross-section are shown
in the graph below. Multi-wire cables with copper forward and return conductors are
used.
The maximum cable lengths for the different cable cross-sections are as follows:
Conductor cross-section
1.5 mm²
2.5 mm²
Max. length
21 m
35 m
Do not use cables where the losses will exceed 1.0%
Cable length
Line l
o
ss
es
Содержание Sunny Boy SB 1100LV
Страница 2: ......
Страница 6: ...Explanation of the symbols used SMA Technologie AG Page 6 SB1100LV 11 SE2006 Installation Guide ...
Страница 8: ...Foreword SMA Technologie AG Page 8 SB1100LV 11 SE2006 Installation Guide ...
Страница 10: ...Safety instructions SMA Technologie AG Page 10 SB1100LV 11 SE2006 Installation Guide ...
Страница 32: ...Installation SMA Technologie AG Page 32 SB1100LV 11 SE2006 Installation Guide ...
Страница 34: ...Opening and closing the Sunny Boy SMA Technologie AG Page 34 SB1100LV 11 SE2006 Installation Guide ...
Страница 44: ...Technical data SMA Technologie AG Page 44 SB1100LV 11 SE2006 Installation Guide ...
Страница 50: ...Replacing the varistors SMA Technologie AG Page 50 SB1100LV 11 SE2006 Installation Guide ...
Страница 54: ...Rating for a line circuit breaker SMA Technologie AG Page 54 SB1100LV 11 SE2006 Installation Guide ...
Страница 58: ...The communications interface SMA Technologie AG Page 58 SB1100LV 11 SE2006 Installation Guide ...
Страница 61: ......