Technical data
SMA
Technologie AG
Page 36
SB1100LV-11:SE2006
Installation Guide
8.2 Grid connection data
Description
Unit
Setting
Nominal output power
P
ACnom
1000 W
Continuous output power
(at 45 °C)
1000 W
Peak output power
P
ACmax
1100 W
Nominal output current
I
ACnom
4.4 A
Harmonic distortion of output
current (at K
Ugrid
< 2 %, P
AC
>
0.5 P
ACNom
)
K
IAC
< 4 %
Short-circuit strength
Grid-side via current regulation
Operating range, grid voltage
U
AC
180 ... 265 V AC
Germany: 198 ... 253 / 260 V AC
a
Operating range, grid frequency
f
AC
45.5 ... 54.5 Hz
Germany: 47.55 ... 50.2 Hz
All-pole isolator grid side
Independent disconnection device
("SMA grid guard 2"), double
implementation
Phase shift angle (based on the
current's fundamental frequency)
cos phi
1
Overvoltage category
III
Test voltage (DC)
1.6 kV (1 s routine testing / 5 s type
testing)
Test surge voltage
4 kV (serial interface: 6 kV)
Own consumption in night mode
0.1 W
a
The Sunny Boy can feed into the public grid at a maximum output voltage of
260 V for brief periods. However, DIN VDE 0126-1-1 stipulates that the
average voltage over 10 minutes must not exceed 253 V. I.e., if the grid
voltage remains constant at 254 V, the inverter is automatically disconnected
from the grid. In this case, contact the local grid operator for assistance.
DIN VDE 0126-1-1 only applies in Germany. See chapter 8.4.3 "Country-
specific parameter settings" (Page 42) for the country-specific preset default
values of your inverter.
Содержание Sunny Boy SB 1100LV
Страница 2: ......
Страница 6: ...Explanation of the symbols used SMA Technologie AG Page 6 SB1100LV 11 SE2006 Installation Guide ...
Страница 8: ...Foreword SMA Technologie AG Page 8 SB1100LV 11 SE2006 Installation Guide ...
Страница 10: ...Safety instructions SMA Technologie AG Page 10 SB1100LV 11 SE2006 Installation Guide ...
Страница 32: ...Installation SMA Technologie AG Page 32 SB1100LV 11 SE2006 Installation Guide ...
Страница 34: ...Opening and closing the Sunny Boy SMA Technologie AG Page 34 SB1100LV 11 SE2006 Installation Guide ...
Страница 44: ...Technical data SMA Technologie AG Page 44 SB1100LV 11 SE2006 Installation Guide ...
Страница 50: ...Replacing the varistors SMA Technologie AG Page 50 SB1100LV 11 SE2006 Installation Guide ...
Страница 54: ...Rating for a line circuit breaker SMA Technologie AG Page 54 SB1100LV 11 SE2006 Installation Guide ...
Страница 58: ...The communications interface SMA Technologie AG Page 58 SB1100LV 11 SE2006 Installation Guide ...
Страница 61: ......