Technical Data
Installation Guide
SBTLHCMS-IEN080411
Page35
8. 3 General Data
For a detailed description of the devices, see the operating instructions.
General data
Protection rating per EN 60529
IP65
Dimensions (w x h x d)
470 mm x 490 mm x 225 mm
(approx.)
Weight
approx. 31 kg
Protective function DC side
All-pole isolator on the DC input side
DC plug connector (ESS optional)
Overvoltage protection
Thermally monitored varistors
Personal protection
Ground
fault
monitoring
(Riso > 1 MOhm)
Reverse polarity protection
Via short circuit diode
Protective function AC side
Short-circuit proofing
Grid-side via current regulation
All-pole isolation on grid side
Independent disconnection device
(SMA grid guard), double imple-
mentation
External interfaces
Data transmission over mains power line
optional
Data transmission over separate data cable
Optional, RS232 / RS485, electri-
cally separated
Wireless data transmission
optional
Содержание SB 4200TL HC
Страница 2: ......
Страница 6: ...Explanation of the Symbols Used SMA Technologie AG Page 6 SBTLHCMS IEN080411 Installation Guide...
Страница 10: ...Safety Instructions SMA Technologie AG Page 10 SBTLHCMS IEN080411 Installation Guide...
Страница 30: ...Installation SMA Technologie AG Page 30 SBTLHCMS IEN080411 Installation Guide...
Страница 44: ...Technical Data SMA Technologie AG Page 44 SBTLHCMS IEN080411 Installation Guide...
Страница 46: ...Inspection of the Electronic Solar Switch SMA Technologie AG Page 46 SBTLHCMS IEN080411 Installation Guide...
Страница 60: ...The Communications Interface SMA Technologie AG Page 60 SBTLHCMS IEN080411 Installation Guide...
Страница 63: ......