5.1 BatFuse A.01 and BatFuse A.03
How to connect the A.01 and A.03 BatFuses:
1.
Remove the lid (see section 6 "Opening and Closing" (Page 28)).
2.
Pull the NH fuse plugs from the bracket using the NH handle (as per VDE 0680-4).
3.
Pierce the outer membrane of the required double membrane adapter with a sharp tool.
4.
Cut and strip the battery cables as well as the charge controller cables.
BatFuse A.01
BatFuse A.03
Maximum number of terminals:
Battery side
2 x M32
per pin
2 x M32 and 2 x M25
per pin
Maximum number of terminals:
Sunny Island side
1 x M 32
3 x M 32
Connection possibilities
Battery side
2 batteries or
1 battery and one charge
controller
2 batteries and 2 charge
controllers
Battery cable cross section
1 x 70 mm
2 x 70 mm· instead of
1 x 185 mm
Charge controller cable cross
section
10 mm
10 mm
DANGER!
Risk of lethal electric arcs
•
Always pull and insert NH fuses with an NH handle (as per DIN VDE 0680-4).