background image

 

www.procontechnology.com.au

                                                 1                                                             Phone: (03) 98306288                         

MEAN WELL DC-DC CONVERTER USER MANUAL

 

 

1. INPUT 
 

1.1 INPUT VOLTAGE 
 
DC to DC converters are widely used all over the world. Many types of products are available for both high and low DC voltage 
input. Before using any DC-DC converter, ensure that the output voltage and current is suitable for the intended load. Verify the 
correct input connections, particularly the polarity, and any other conditions that might affect the unit's operation.  
 
If an input voltage is applied which is different from the converter's rating, the unit may be damaged. Also remember that if the 
input voltage is not pure DC, the device may not operate normally. Only the Meanwell SD-100D and SD-150D, type D input 
converters allow an AC input (85~132VAC). 
 
For all Mean Well Models refer to the label on the converter for the input voltage range. 
 
1.2 INPUT CURRENT 
 
The essential difference between an AC to DC power supply and a DC to DC converter is not just that the DC-DC converter 
generally uses lower input voltages but that it does not require rectification of AC to DC nor does it require AC power factor 
correction circuitry. Standard DC to DC converters simply filter the Direct Current (DC) input which then charges a smoothing 
or filtering capacitor. The input current required is determined by the output power, input voltage and efficiency. The simplest 
input stage with reverse polarity fuse protection is shown below:  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 2 

 
Not all Meanwell DC-DC converters have reverse polarity input protection. The simplest form of protection is a fuse and a 
diode; if necessary the user may provide these components externally. The latest Meanwell high-wattage DC-DC converters 
(RSD and DDR series) use a MOSFET circuit that tolerates accidental polarity reversal without damaging the unit. 
 
Also not all DC-DC converters have sufficient EMI (Electromagnetic Interference) filtering and may require external filtering 
of the input to meet regulatory requirements. Please refer to the data sheet. 
 
1.3 INRUSH CURRENT 
 
When power is applied, a large current flows to charge the input smoothing or filter capacitor. This current is called the "inrush 
current". The value of the inrush current varies according to the size of the smoothing capacitor and the presence or absence of 
the inrush current protection devices. The inrush current is many times larger than the normal input current. The more DC-DC 
converters used in the same system, the larger the inrush current. Please ensure that fuses, switches, and other parts connected to 
the input supply side are appropriately selected. Also, when powering DC-DC converters from other DC sources you will need 
to allow for this inrush current and make allowance for the switch-on sequence of multiple converters. 
 
If the converter's fuse is blown, do not replace the fuse and operate the unit before rectifying the problem that caused it to fail – 
otherwise further damage may occur! Always replace the fuse with the same rated type. Always remove power to the unit and 
discharge the input smoothing capacitor before attempting to replace the fuse. 
 
 

Содержание DDR-120B-12

Страница 1: ... Fig 2 Not all Meanwell DC DC converters have reverse polarity input protection The simplest form of protection is a fuse and a diode if necessary the user may provide these components externally The latest Meanwell high wattage DC DC converters RSD and DDR series use a MOSFET circuit that tolerates accidental polarity reversal without damaging the unit Also not all DC DC converters have sufficien...

Страница 2: ...an result Types of Protection a Foldback Current Limiting The Foldback Current Limiting circuit is designed to linearly decrease both the voltage and current to a level that will prevent the unit from being damaged during overcurrent overload conditions See curve a in Fig 4 b Constant Current Limiting Constant Current Limiting allows the output current to remain stable but reduces the output volta...

Страница 3: ...perature condition is removed high ambient temperature and or high load 2 4 OVER VOLTAGE PROTECTION OVP When the output voltage exceeds the rated value by approximately 130 the unit will be protected by the following three possible methods to prevent damage to the components at the load terminals a Shut down the output voltage Reset the DC DC converter by turning it OFF for several seconds and the...

Страница 4: ...any device please refer to any notes and temperature derating curves in the specifications For example with DIN rail converters the minimum installation clearances are 40mm on top 20mm on the bottom 5mm on the left and right sides unless the adjacent device is also a heat source then 10 15mm clearances are recommended Output Derating Output power depends on operating temperature Derate the output ...

Страница 5: ...that the converter not be mounted until all work has been completed or the vents are covered until the converter is ready to be operated Fig 9 Ground connection Connect the ground terminal of the DC DC converter to the frame of the equipment with regulation size and colour wire to ensure safety and to minimize noise and interference Fig 10 Inrush Current Control Mean Well DC DC converters have lar...

Страница 6: ...e able to detect any voltage drop at the load The unit will raise the output until the correct voltage is provided at the load terminals Remote sensing compensates for voltage drops of up to 0 5V Fig 12 Operation in Parallel Power supplies are commonly used in parallel to increase the output current Mean Well s DDR 240 and DDR 480 series are designed for parallel use These power supplies have P an...

Страница 7: ...in series to produce higher voltages Two types of series connections are described below For series operation all DC DC converters require floating or isolated outputs a Fig 15 describes a sample setup for separate distinctive loads Protective diodes D1 and D2 below may be necessary with this type of application to protect the units if connection X is lost Fig 15 b Fig 16 illustrates a sample setu...

Страница 8: ...pacitors and control the output ripple Their values should be between 47uf and 100uf C2 C4 C5 C6 are high frequency ceramic capacitors and reduce the output noise Their values range from 0 01uf and 0 1uf The value of inductance L1 is 0 5uH to 5uH Surge Voltage Control Fig 18 shows a circuit used to control voltage surges that may be caused by power fluctuations or stray surges due to lightning The...

Страница 9: ...Voltage The input voltage of the DC DC converter by design is limited It can be dangerous to apply voltage which is outside of the specified range damage may occur to the unit Always operate it within its specified input voltage range Always check the polarity of the input voltage before applying power Leakage Current The internal noise filter capacitors generate a leakage current within the range...

Страница 10: ...d output sides of the DC DC converter Ground Wire Connect the grounding terminal of the unit to the frame of the equipment with a short thick wire Note For DC DC converters integrated into other equipment safety standards differ from country to country Check the standards specifications listed in documents provided by your supplier or relevant government agency when you use a converter inside your...

Страница 11: ...ITY 6 1 LIFE CYCLE AND BREAKDOWN DC DC converters have proven to be highly reliable when used in household appliances and industrial products and are highly rated throughout industry The following figure shows the failure rate curve bathtub curve during a typical product life cycle The Early Failure Period to prevent early failure each manufacturer screens out parts or performs aging tests on the ...

Страница 12: ...d continuously In this case the frequency of overhauls to the DC DC converter should be as follows Ta is between 40ºC and 45ºC once every three years Ta is between 35ºC and 40ºC once every four years Ta is between 30ºC and 35ºC once every five years Where Ta indicates the ambient temperature of the DC DC converter The above temperature values may differ depending on the type of DC DC converter use...

Страница 13: ...of this information for their application We strongly advise all customers to contact us for advice on the most suitable DC DC converter for their needs It is especially important that the correct DC DC converter is used and protective circuits are installed when driving heavily inductive or capacitive loads including motors DC to DC converters and other loads with high inrush current such as lamp...

Отзывы: