background image

 

www.procontechnology.com.au

                                                 7                                                             Phone: (03) 98306288                         

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 14 

 
Figure 14 illustrates a method of paralleling DC-DC converters for redundant use - increasing the reliability of a system. Diodes 
are connected to the positive side of each unit's output. This connection is only for use in redundant systems, where the 
maximum current requirement can be handled by one unit alone, and allows the system to continue to operate even when one 
unit fails. Also see the Meanwell DRDN20 for 20A and the DRDN40 for 40A applications. These modules provide a DC OK 
indication and alarm relay contacts. 
 
Operation in Series 
 
DC-DC converters are often connected in series to produce higher voltages. Two types of series connections are described 
below. For series operation all DC-DC converters require 'floating' or isolated outputs!  
 
a. Fig. 15 describes a sample setup for separate distinctive loads. Protective diodes (D1 and D2 below) may be necessary with 
this type of application to protect the units if connection X is lost.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 15 

 
b. Fig. 16 illustrates a sample setup for series connected DC-DC converters. The diode, connected directly across the output 
terminals, is also recommended in any application where a reverse voltage may be applied to the unit's output. As a general 
guide, the diodes should be Schottsky Barrier with a reverse voltage more than twice the output voltage and rated output current 
more than twice the rated output current or short-circuit current whichever is greater. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig. 16 

 
 
 

Содержание DDR-120B-12

Страница 1: ... Fig 2 Not all Meanwell DC DC converters have reverse polarity input protection The simplest form of protection is a fuse and a diode if necessary the user may provide these components externally The latest Meanwell high wattage DC DC converters RSD and DDR series use a MOSFET circuit that tolerates accidental polarity reversal without damaging the unit Also not all DC DC converters have sufficien...

Страница 2: ...an result Types of Protection a Foldback Current Limiting The Foldback Current Limiting circuit is designed to linearly decrease both the voltage and current to a level that will prevent the unit from being damaged during overcurrent overload conditions See curve a in Fig 4 b Constant Current Limiting Constant Current Limiting allows the output current to remain stable but reduces the output volta...

Страница 3: ...perature condition is removed high ambient temperature and or high load 2 4 OVER VOLTAGE PROTECTION OVP When the output voltage exceeds the rated value by approximately 130 the unit will be protected by the following three possible methods to prevent damage to the components at the load terminals a Shut down the output voltage Reset the DC DC converter by turning it OFF for several seconds and the...

Страница 4: ...any device please refer to any notes and temperature derating curves in the specifications For example with DIN rail converters the minimum installation clearances are 40mm on top 20mm on the bottom 5mm on the left and right sides unless the adjacent device is also a heat source then 10 15mm clearances are recommended Output Derating Output power depends on operating temperature Derate the output ...

Страница 5: ...that the converter not be mounted until all work has been completed or the vents are covered until the converter is ready to be operated Fig 9 Ground connection Connect the ground terminal of the DC DC converter to the frame of the equipment with regulation size and colour wire to ensure safety and to minimize noise and interference Fig 10 Inrush Current Control Mean Well DC DC converters have lar...

Страница 6: ...e able to detect any voltage drop at the load The unit will raise the output until the correct voltage is provided at the load terminals Remote sensing compensates for voltage drops of up to 0 5V Fig 12 Operation in Parallel Power supplies are commonly used in parallel to increase the output current Mean Well s DDR 240 and DDR 480 series are designed for parallel use These power supplies have P an...

Страница 7: ...in series to produce higher voltages Two types of series connections are described below For series operation all DC DC converters require floating or isolated outputs a Fig 15 describes a sample setup for separate distinctive loads Protective diodes D1 and D2 below may be necessary with this type of application to protect the units if connection X is lost Fig 15 b Fig 16 illustrates a sample setu...

Страница 8: ...pacitors and control the output ripple Their values should be between 47uf and 100uf C2 C4 C5 C6 are high frequency ceramic capacitors and reduce the output noise Their values range from 0 01uf and 0 1uf The value of inductance L1 is 0 5uH to 5uH Surge Voltage Control Fig 18 shows a circuit used to control voltage surges that may be caused by power fluctuations or stray surges due to lightning The...

Страница 9: ...Voltage The input voltage of the DC DC converter by design is limited It can be dangerous to apply voltage which is outside of the specified range damage may occur to the unit Always operate it within its specified input voltage range Always check the polarity of the input voltage before applying power Leakage Current The internal noise filter capacitors generate a leakage current within the range...

Страница 10: ...d output sides of the DC DC converter Ground Wire Connect the grounding terminal of the unit to the frame of the equipment with a short thick wire Note For DC DC converters integrated into other equipment safety standards differ from country to country Check the standards specifications listed in documents provided by your supplier or relevant government agency when you use a converter inside your...

Страница 11: ...ITY 6 1 LIFE CYCLE AND BREAKDOWN DC DC converters have proven to be highly reliable when used in household appliances and industrial products and are highly rated throughout industry The following figure shows the failure rate curve bathtub curve during a typical product life cycle The Early Failure Period to prevent early failure each manufacturer screens out parts or performs aging tests on the ...

Страница 12: ...d continuously In this case the frequency of overhauls to the DC DC converter should be as follows Ta is between 40ºC and 45ºC once every three years Ta is between 35ºC and 40ºC once every four years Ta is between 30ºC and 35ºC once every five years Where Ta indicates the ambient temperature of the DC DC converter The above temperature values may differ depending on the type of DC DC converter use...

Страница 13: ...of this information for their application We strongly advise all customers to contact us for advice on the most suitable DC DC converter for their needs It is especially important that the correct DC DC converter is used and protective circuits are installed when driving heavily inductive or capacitive loads including motors DC to DC converters and other loads with high inrush current such as lamp...

Отзывы: