13 Technical Data
SMA Solar Technology AG
100
STP5-9TL-IA-en-10
Installation Manual
13.2 General Data
13.3 Protective Devices
Width x height x depth with
Electronic Solar Switch
470 mm x 730 mm x 240 mm
Weight
37 kg
Length x width x height of packaging
798 mm x 598 mm x 398 mm
Transport weight
40 kg
Climatic category (according to IEC 60721-3-4)
4K4H
Operating temperature range
− 25°C … +60°C
Maximum permissible value for relative humidity,
non-condensing
100%
Maximum operating altitude above MSL
3,000 m
Noise emission (typical)
≤ 40 dB (A)
Power loss in night operation
1 W
Topology
Transformerless
Cooling concept
OptiCool
Fan connection
Designed for safe disconnection in accordance
with DIN EN 50178:1998-04
Degree of protection for electronics according to
IEC 60529
IP65
Protection class (according to IEC 62103)
I
Licences (as per 06/2012)
CE, VDE-AR-N 4105, VDE0126-1-1/
UTE C15-712-1
Planned licences (as per 06/2012)
RD 1699, RD 661/2007, PPC, AS4777,
EN 50438* , C10/11, MEA, PPDS, SI4777,
G83/1-1, PEA
* Does not apply for all national appendices of EN 50438
DC reverse polarity protection
Short-circuit diode
Input-side disconnection device
Electronic Solar Switch, SUNCLIX DC connector
DC overvoltage protection
Thermally monitored varistors
AC short-circuit current capability
Current control
Grid monitoring
SMA Grid Guard 4
Maximum permissible fuse protection
32 A
Earth fault monitoring
Insulation monitoring: R
iso
> 385 kΩ
All-pole sensitive residual-current monitoring unit
Available