6 Electrical Connection
SMA America, LLC
48
SB3-5TLUS22-IA-en-10
Installation Manual
6.5 Connecting the Emergency Power Module
Connection principle
Additionally required mounting material (not included in the scope of delivery):
☐ Switch to activate the emergency power socket-outlet designed for at least 120 V (AC) and
10 A
☐ Switch to activate the emergency power socket-outlet
☐ 1 listed conduit fitting (
3
⁄
4
in. (19 mm)), for outdoor installation rain-proof or moisture-proof
☐ 1 listed conduit (
3
⁄
4
in. (19 mm))
Cable Requirements
☐ 5 conductors must be available.
☐ The insulated conductors for the switch must be of a different color than the insulated conductors
of the socket-outlet.
☐ Comprising copper in the form of solid or stranded wire, not fine-stranded wire.
☐ Conductor cross-section: 16 AWG to 12 AWG (1.5 mm² to 3.3 mm²)