7 Commissioning
SMA America, LLC
54
SB3-5TLUS22-IA-en-10
Installation Manual
7.1.2 Changing the Country Data Set and the Display Language
If the default country data set of the inverter does not apply to your country, then you must change
the country data set and the display language.
1. When the inverter is in operation, disconnect it (see Section 8).
2. Set the rotary switches
A
and
B
to the desired
position using a slotted screwdriver
(blade width: 2.5 mm) (see Section 7.1.1
"Overview of the Rotary Switches", page 52).
3. Commission the inverter (see Section 7.2).
☑ The inverter will adopt the setting after commissioning. This can take up to 5 minutes.
D
2
Island mode 60 Hz
French
D
3
Island mode 60 Hz
Spanish
D
4
Island mode 60 Hz
Italian
D
5
Island mode 60 Hz
Greek
D
6
Island mode 60 Hz
Czech
E
0
Island mode 50 Hz
English
E
1
Island mode 50 Hz
German
E
2
Island mode 50 Hz
French
E
3
Island mode 50 Hz
Spanish
E
4
Island mode 50 Hz
Italian
E
5
Island mode 50 Hz
Greek
E
6
Island mode 50 Hz
Czech
* The country data set is automatically blocked after 10 feed-in hours. You can then only change the country data set by
inputting the personal access code you received from SMA on a communication device.
Rotary switch A
position
Rotary switch B
position
Country data set
Display language