Technical Data
SMA
Technologie AG
Page 90
SMC50A_60A-IEN073320
Installation Guide
Sunny Mini Central SMC 6000A
The parameters listed below represent country-specific settings and are only displayed
in installer mode. All other parameters are international and can be viewed in the table
in section 14.4.2.
Name
Short
descr.
Country settings
Germany
Australia
Great
Britain
Italy
Spain
ACVtgRPro
V
253
253
253
253
253
Default
GER/
VDE0126-1-1
AUS/
AS4777
GB/
G83
IT/
DK5950
SP/
RD1663
dFac-Max
Hz/s
4
0.25
0.2
0.20
2
dZac-Max mOhm
670
20000
350
350
350
Fac-delta-
Hz
2,45
0,19
0.5
0.29
0.98
Fac-delta+
Hz
0,19
0,19
0.5
0.29
0.98
I-Ni-Test
mA
16000
8000
0
0
0
LDVtgC
V
0
50
0
50
50
T-Start
s
10
45
180
10
10
Uac-Min
V
198
205
209
198
199
Uac-Max
V
260
265
261
262
250