Grid Connection Data
Nominal output power
P
ACnom
6000 W
Peak output power
P
AC, max
6000 W
Nominal output current
I
ACnom
26 A
Max. output current
I
AC, max
26 A
Harmonic distortion of output current
(at KUgrid < 2 %,
PAC > 0.5 PACnom)
K
IAC
< 4 %
Short-circuit proofing
current control
Nominal operational voltage
U
ACnom
230 V
Operating range, grid voltage
(complying with
DIN VDE 0126-1-1)
U
AC
198 ... 253 V / 260 V
a
Voltage range
(extended operating range)
U
AC
180 V - 265 V
Nominal operating frequency
f
ACnom
50 Hz / 60 Hz
Operating range, grid frequency
(complying with
DIN VDE 0126-1-1)
f
AC
47.5 Hz - 50.2 Hz
Frequency range
(extended operating range)
f
AC
50 Hz: 45.5 Hz - 54.5 Hz
60 Hz: 55.5 Hz - 64.5 Hz
All-pole isolator on grid side
automatic disconnection device
(SMA grid guard 2)
Power factor
cos phi
1
Overvoltage category
III
Test voltage (50 Hz)
2 kV
Test surge voltage
4 kV (serial interface: 6 kV)
Operating consumption in night
mode
0.25 W