5.1 Selecting an Installation Location
No.
Checkpoint
Control
Location
1
The installation location and
method of installation is suitable for
the weight of approximately 63 kg
and the dimensions of
468 mm x 613 mm x 242 mm
(width x height x depth) of the
Sunny Mini Central.
2
The following minimum clearances to walls, other devices or
objects must be observed to guarantee sufficient heat dissipation.
Direction
Minimum
clearance
Sides
30 cm
Top
30 cm
Underside
50 cm
Front
5 cm
468 m
m
24
2
mm
61
3
m
m
63 kg