SMA
Technologie AG
Technical Data
Installation Guide
SMC50A_60A-IEN073320
Page 87
14.4.2 Parameter Settings for Germany
Grayed out parameters are only displayed in installer mode. The table below contains
the parameters that are applicable in Germany.
Name
Short
descr.
Value range
Default setting
SMC 5000A
SMC 6000A
ACVtgRPro
V
230 ... 300
253
253
AntiIsland-
Ampl *
grd
0 ... 10
0
0
AntiIsland-
Freq *
mHz
0.1 ... 2000
500
500
Betriebsart
MPP, Ikonst, Stop,
Turbine Mode,
U-konst, Off_grid
MPP
MPP
Control
Auto, Grid,
Bridge
Auto
Auto
Default *
GER/VDE0126-1-1,
GB/G83,
AUS/AS4777,
USA/UL1741,
IT/DK5950,
Off_Grid,
SP/RD1663,
Other, trimmed
GER/VDE0126-1-1 GER/VDE0126-1-1
dFac-MAX *
Hz/s
0.1 ... 4.0
4
4
dZac-MAX *
mOhm 0.35 ... 20000
685
670
E_Total
kWh
0 ... 200000
0
0
Fac-delta- *
Hz
0.1 ... 4.5
2.45
2.45
Fac-delta+ *
Hz
0.1 ... 4.5
0.19
0.19
Fac-Limit delta Hz
0 ... 5
2
2
Fac-Start delta Hz
0 ... 5
1
1
Fan test
0 ... 1
0
0
h_Total
h
0 ... 200000
0
0
Inst.-Code
I-NiTest *
mA
0 ... 25000
16000
16000