SENSOR OPERATION

After power is applied, the Sensor Module will perform its Start-up routine for 15 seconds with LED blinking.
NOTE: A three (3) seconds long Red LED, followed by slow Red LED blinking in the Sensor Window indicates sensor is in the start-up mode. There
will be two (2) Red LED pulses (each two (2) seconds long) in the Sensor Window to indicate the start-up routine is complete.
After the start-up routine is complete, in the first ten (10) minutes of operation, a visible Red LED flashes in the Sensor Window of the CX
Flushometer when a user is detected.

The CX Flushometer has a factory set sensing range:
i. Water Closet Models – 22” to 31” (559 mm to 787 mm)
ii. Urinal Models – 9” to 21” (229 mm to 533 mm)
Test sensor by stepping in front of the sensor for 10 seconds.

After 10 seconds step away from the sensor and listen for a “CLICK”
The factory setting should be satisfactory for most installations. If a range adjustment is required, refer to the range adjustment instructions in this
installation guide (See page 13).

TEST SENSOR OPERATION

Flushometer is shipped with the flow control adjustment turned OFF.

Disconnect Flushometer Solenoid connector from the Sensor Assembly

Lift the Sensor Assembly Override Button up to access the activation assembly.

Open water flow by turning activation assembly slowly COUNTERCLOCKWISE using 

adjusting tool and a screwdriver or a wrench.

Connect Flushometer Solenoid connector to the Sensor Assembly.

Activate Flushometer by pressing the Override Button.

Adjust Activation Assembly after each flush until the flow rate 
delivered properly cleanses the fixture (turn CLOCKWISE to lessen 
flow and COUNTERCLOCKWISE to increase flow).

A

B

A
B

C

A

B

D

E

F

CLOSE

OPEN

ADJUST WATER FLOW

11

Содержание CX 8158-1.28

Страница 1: ...lushometers CX 8158 1 6 CX 8158 1 28 ITEMS INCLUDED VALVE BOX 1 Valve Box 2 Mud Guard 3 Adjustment tool 4 Mud Guard Screws 5 Activation Assembly Screws 6 Instructions 7 Adjustable Tube 8 Outlet Connec...

Страница 2: ...ELECTED Consult fixture manufacturer for minimum pressure requirements Most Low Consumption water closets 1 6 gpf 6 0 Lpf require a minimum flowing pressure of 25 psi 172 kPa Model 8158 Closet Wall Hu...

Страница 3: ...W FRONT VIEW Model 8158 Closet Floor Mount Rear Inlet Roughin for Sloan CX is determined relative to the spud connection for the fixture being used THIS PRODUCT CONTAINS MECHANICAL COMPONENTS THAT ARE...

Страница 4: ...uard Metal C Bracket Wall Bracket Outlet Connection Gasket Poly Washer Elbow Poly Washer Coupling Adjustable Tube V500A RB Vacuum Breaker Assembly Vacuum Breaker Kit Valve Body Wall Box Shut off Sleev...

Страница 5: ...T EXERT FORCE ON WALL BOX TO TIGHTEN FLUSHOMETER USED FIXED JAW WRENCH TO HOLD THE VALVE For hardwire use only remove wall box knock cap closest to the conduit connection E Using a sweat union not sup...

Страница 6: ...secure it to the wall box Run transformer wires through the conduit to the wall box NOTE TRANSFORMER NOT PROVIDED IT IS VERY IMPORTANT THAT THE OUTPUT VOLTAGE OF THE TRANSFORMER BE 6VAC FOR THE UNIT T...

Страница 7: ...eaker casing Flush Connection Wall opening 1 If needed trim urinal flush tube 2 Slide 3 4 coupling over urinal flush tube If cutting tube thread adapter first then cut After cut remove adapter to help...

Страница 8: ...press until fully seated Remove screws CLOSE E1 E2 B2 B1 C B3 D D G H G1 OPEN CLOSE G Reinstall Collar Collar will spin freely in valve body when properly installed H Using adjustment tool turn activa...

Страница 9: ...Blue terminal block to the two pins in the back of the Sensor Assembly IMPORTANT SURGE PROTECTOR BEFORE THE TRANSFORMER IS RECOMMENDED iii iv One EL 386 Transformer sold separately serves one 1 CX Clo...

Страница 10: ...l bracket is positioned plumb and level before tightening the screws completely The Sloan CX sensor assembly is designed to work with both hardwire and battery as a back up or only the battery power c...

Страница 11: ...seconds After 10 seconds step away from the sensor and listen for a CLICK The factory setting should be satisfactory for most installations If a range adjustment is required refer to the range adjustm...

Страница 12: ...e Make sure Wall Plate doesn t slide up A B C OPERATION A continuous INVISIBLE light beam is emitted from the Sloan CX Sensor After the user enters the beam s effective range 22 to 31 inches 559 mm to...

Страница 13: ...solenoid connector from the sensor assembly C Shut off water use adjustment tool to turn activation assembly fully clockwise Pass solenoid wire through center of tool to avoid damage Remove tool when...

Страница 14: ...Times When User Steps Within Range Battery Only i Batteries low replace batteries F Red Light Blinks four 4 Times When User Steps Within Range Hardwire and Battery i Battery box not connected connect...

Страница 15: ...306392PK Elbow 6 3306002 1 1 2 Coupling with S 21 Gasket 7 0306031PO 1 1 2 38 mm Flanged outlet tube RB 6 8 0396669PK F 102 1 1 2 38 mm Outlet Tube CP 8 9 0306238PK F 7 Flange CP 10 0306146PK F 5 A 1...

Отзывы: