background image

V

ICTORY 

II 

VHS Models

26

APPENDIX A

Vent System Location and Condensation

Drain Requirements

1. The venting system shall terminate at least 3 feet

above any forced air inlet located within 10 feet.

2. The venting system shall terminate at least 4 feet

below, 4 feet horizontally from, or 1 foot above any
door, window or gravity air inlet into any building.
The bottom of the vent terminal shall be at least 12
inches above grade or the normal snow level,
whichever is greater.

3. Through the wall vents for Category II and IV appli-

ances shall not terminate over public walkways or
over areas where condensate or vapor could create
a nuisance or hazard or could be detrimental to the
operation of regulators, relief valves or other equip-
ment. Minimum clearance of 4' horizontally from,
and in no case above or below, unless a 4' horizon-
tal distance is maintained, from electric meters, gas
meters, regulators and relief equipment. Where
local experience indicates that condensate may be
a problem with Category 

I

and 

III

appliances, this

provision shall also apply.

4. Provision shall be made to collect and dispose of

condensate from venting systems serving Category

I, II, III

and 

IV

appliances.

Caution
Flue gases exiting from the vent terminal will con-
dense. Building materials in the area of the vent termi-
nal should be protected from discoloration and degra-
dation.

APPENDIX B

Removal of Existing Boiler From 

Common Vent System

a. Seal any unused openings in the common venting

system.

b. Visually inspect the venting system for proper size

and horizontal pitch and determine there is  no
blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.

c. Insofar as is practical, close all building doors and

windows and all doors between the space in which
the appliances remaining connected to the com-
mon venting system are located and other spaces
of the building. Turn on clothes dryer and any appli-
ance not connected to the common venting sys-
tem. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate
at maximium speed. DO NOT operate a summer
exhaust fan. Close fireplace dampers.

d. Place in operation the appliance being inspected.

Follow the lighting instructions. Adjust thermostat 
so appliance will operate continuously.

e. Test for spillage at the draft hood relief opening 

after 5 minutes of main burner operation. Use the 
flame of a match or candle, or smoke from a ciga-
rette, cigar or pipe.

f.

After it has been determined that each appliance 
remaining connected to the common venting sys-
tem properly vents when tested as outlined above, 
return doors, windows, exhaust fans, fireplace 
dampers and any other gas burning appliance to 
their previous conditions of use.

g.

Any improper operation of the common venting 

system should be corrected so the installation con-
forms with the National Fuel Gas Code, ANSI 
Z223.1-latest edition. When resizing any portion of 
the common venting system, the common venting 
system should be resized to approach the mini-
mum size as determined using the appropriate 
tables in Appendix G in the National Fuel Gas 
Code, ANSI Z223.1-latest edition.

Содержание VHS-180

Страница 1: ...is under positive pres sure when it is connected to the outdoors with 3 diameter pipe Leakage from this system can be hazardous and if not avoided can result in death or serious injury In addi tion to...

Страница 2: ...b Gas Type 2000 3000 4000 5000 6000 7000 8000 9000 10000 Orifice Size for Sea Level Orifice Sizes for High Altitudes Includes 4 Reduction for Each 1000 Feet Elevation Feet Orifice sizes indicated for...

Страница 3: ...ces so fueled shall not be installed in an above grade under floor space or basement unless such loca tion is provided with an approved means for removal of unburned gas Consult Chapter 5 of the 1994...

Страница 4: ...g with a minimum FREE air passage area of 1 square inch per 1000 Btuh of total appliances input IF BOILERS ARE INSTALLED ADJACENT TO OTHER FUEL BURNING EQUIPMENT THE AREA OF FREE OPENINGS MUST BE APPR...

Страница 5: ...mble Part Numbers and more information B Vertical Venting Figure 7 shows typical vertical venting A fire stop is required for each ceiling and floor penetration An existing chimney see Figure 8 may be...

Страница 6: ...Ft Altitudes 5500 to 7000 Ft Altitudes 7000 to 10 000 Ft Altitudes Equivalent Length of each 90 Elbow Ft Max Equivalent Length Ft VHS 30 30 30 30 6 2 60 90 and 120 VHS 150 30 30 15 6 2 VHS 180 30 15 1...

Страница 7: ...of Snow Line Knowledge of local conditions will reveal the maximum height that repeated snowfalls accumulate to The height should be used as the SNOW LINE Definition of Snow Line Knowledge of local co...

Страница 8: ...VICTORY II VHS Models 8 Figure 7...

Страница 9: ...VICTORY II VHS Models Figure 8 9...

Страница 10: ...to an unlined masonry chimney If a masonry chimney is exposed to the outdoors on one or more sides below the roof line exposed chimney it must be re lined with a UL listed metallic liner system See Ta...

Страница 11: ...ey height VHS 180 and connector length restrictions 10 9 1999 edition 2 Connector may have to be upsized to 6 diameter to meet requirement of 10 9 Additional National Fuel Gas Code Boiler Gas Applianc...

Страница 12: ...VICTORY II VHS Models 12 Figure 9...

Страница 13: ...VICTORY II VHS Models Figure 10 13...

Страница 14: ...dix C of National Fuel Gas Code ANSI Z223 1 latest edition C The boiler and its gas connection must be leak tested before placing the boiler in operation Use liquid soap solution for all gas leak test...

Страница 15: ...sizes see dimensions on page 2 Shut off valves are recommended 2 Circulating Systems Victory II boilers are equipped with a water circulating pump mounted to the return water connection on the boiler...

Страница 16: ...VICTORY II VHS Models 16...

Страница 17: ...VICTORY II VHS Models Figure 14 Figure 15 Piping Arrangement 17...

Страница 18: ...er equipment PIPING A HEATING COOLING SYSTEM TO A WATER BOILER AND CHILLER Figure 16 illustrates a method of piping a heating cooling sys tem to a water boiler and a chiller Hand valves shown or autom...

Страница 19: ...9 Set thermostat to desired setting 10 If appliance will not operate follow the instructions To Turn Off Gas To Appliance and call your service or gas supplier To Turn Off Gas to Appliance 1 Set therm...

Страница 20: ...ports are on top of main burner tube C Main Burner Ignition Checkout and Pilot Adjustment 1 The pilot flame must not smother or snuff out when tested as follows a Main burner ignition from cold start...

Страница 21: ...This section must be brought to the attention of the owner by the installer so that the owner can make the necessary arrangements with a qualified service agency for the periodic care and maintenance...

Страница 22: ...d on burners to collect any foreign material in cleaning flues 1 Remove control box see instruction under Safety Check See Figure 20 2 Remove jacket top 3 Remove inducer assembly 4 Remove flue collect...

Страница 23: ...OR CONTINUES TO RUN NATURAL GAS S8600F IGNITION SPARK CONTINUES PILOT VALVE REMAINS OPEN UNTIL SYSTEM IS RESET SPARK GENERATOR OFF MAIN VALVE OPENS MODULE MONITORS PILOT FLAME NO NO NO NO YES YES YES...

Страница 24: ...e blower motor 8 Check voltage 120V at motor connector Replace defective motor 9 Defective transformer 9 Replace Aquastat 10 Defective gas valve 10 Replace BURNERS WILL NOT SHUT OFF CAUSE REMEDY 1 Def...

Страница 25: ...nd venting system 4 Condensation trap is not full of water 4 Check and fill with water 5 Venting system is physically damaged 5 Check carefully and repair Also see Venting System Regular Inspection 6...

Страница 26: ...ystem b Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe...

Страница 27: ...SLANT FIN CORPORATION Greenvale N Y 11548 Phone 516 484 2600 FAX 516 484 5921 Canada Slant Fin LTD LTEE Mississauga Ontario www slantfin com...

Отзывы: