Alternate Sidewall venting for direct or non-direct venting:
Vent and/or air intake piping may be installed per figure 12a
in order to provide enough clearance from snow line.
Maximum allowed equivalent vent and air intake length for all
of the approved vent and air intake materials is 30.48 m
(100 ft.).
Figure12a: Sidewall venting and air intake piping
305 MM (12") MIN.
406 MM (16") MAX.
305 MM (12") MIN.
508 MM (20") MAX.